UPS WITH BYPASS ELECTRICAL INSTALLATION
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
28
6. Install the conduit adapters. AC input and AC output conductors
must be run through separate conduits. UPS output circuits must
be installed in dedicated conduit systems and not shared with other
electrical circuits.
Figure 15 shows input and output wiring terminals inside the Eaton
9170+ UPS cabinet.
321
+DC X1X2
N
-DC
N
-DC
X2
+DC X1
Backplane Board
Terminating
Studs
X3
Figure 15. UPS Input and Output Terminals