- Eaton UPS User's Guide

UPS STARTUP
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
69
Startup for Plug-Receptacle Units
To start a plug-receptacle unit:
1. Plug the power cable of the unit into an approved, functional power
outlet.
2. If external battery cabinets are installed, check the cable
connections between the UPS and external battery cabinets.
Close the DC disconnect switch button on the back of each external
battery cabinet. Insert the switch key supplied with the cabinet into
the button and turn clockwise 1/2-turn. Pull the button out to close
the switch. Turn the key back counter-clockwise, and remove the
key.
3. Ensure that all power modules are properly installed and latched
into the UPS cabinet.
4. If you are installing power management software, connect your
computer to the UPS communication port (shown in Figure 49)
using the supplied communication cable.
DB-9 Communication Port
for Computer Cable
Figure 49. Communication Port
5. The UPS front panel display automatically turns on whenever input
power is present and at least one power module is installed. Set up
the initial operating parameters through the front panel display (see
Initial Startup Parameters” on page 74).
NOTE The unit has no physical On/Off switch. Access the UPS On/Off function through the
front panel display.
NOTE If the UPS has been manually set to operate in Bypass or Battery mode, change the
System Control Mode Preference (menu 4 1) selection to Auto to return to normal Auto mode
operation.