- Eaton UPS User's Guide

OPERATION
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
84
Reading the Eaton 9170+ System Logs
The Eaton 9170+ system makes an entry in its logs each time it sounds
an alarm or runs on battery power. This information can help in
diagnosing power problems. You can display the UPS Inverter and Alarm
logs on the front panel display in menu 2.
Inverter Log
The inverter (Battery mode) log is in menu 2 1. Move through the menu
structure by pressing the Menu button and pressing the
B
button to
move down to menu 2. Press
to move to submenu 1 and press
again to view the most recent entry in the inverter log.
The log stores up to 10 entries, in chronological order. Use the
B
and
Y
buttons to scroll up and down through the log entries. Each entry shows
the date and time the unit switched to battery operation (in 24-hour
format) and the duration of battery operation (in hours and minutes).
A typical Inverter Log entry is shown in Figure 57:
2 1 1 #0
I 09/29 13:56 01:04
Line Fault
Slot Top ESC
Figure 57. Inverter Log Entry
Figure 57 displays the most recent inverter log (2 1 1). If the unit is still
running on inverter (battery power), an asterisk (*) appears beside the
date. The Battery mode operation occurred on “09/29” (September 29)
at “13:56” (1:56 p.m.), and the batteries supplied power for “01:04”
(1 hour and 4 minutes).
Table 11 lists the inverter messages.
Table 11. Inverter Log Messages
Message Explanation
Line Fault UPS switched to battery because the input voltage was too high or low.
Battery Test Battery test initiated inverter operation.
Manual Operator initiated inverter operation.