- Eaton UPS User's Guide

COMMUNICATION
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
90
ConnectUPSt Web/SNMP Card (BD Model)
The ConnectUPS-BD Web/SNMP Card provides the Eaton 9170+
system with its own ethernet network connection, allowing it to be
remotely monitored and controlled via industry-standard Internet
browsers. The HTML interface enables UPS monitoring and
management from anywhere on the Internet or within your intranet. In
addition, third-party Simple Network Management Protocol (SNMP)
software packages may also be used to communicate remotely with the
Eaton 9170+ system.
The ConnectUPS-BD Web/SNMP Card also allows UPS-dependent
computer systems to automatically shut down during extended power
outages using the NetWatch client software provided on the Software
Suite CD or Web site.
Relay Interface Card (BestDock Model)
The BestDock Relay Interface Card provides true relay contact output to
peripheral devices. Outputs are user-selectable as normally open or
normally closed. Refer to the instructions included with the relay card for
more detail.
Dedicated Input Signals
Emergency Power-off: Connection to a facility Emergency Shutdown
switch provides a method for emergency Eaton 9170+ system
shutdown. Opening this connection creates an immediate shutdown of
the Eaton 9170+ UPS output.
Bypass: The signal from an external bypass switch, to isolate the Eaton
9170+ system for maintenance purposes, tells the UPS to go into
Internal Bypass mode.