Data Sheet

Overvoltage category/pollution degree III/3
Rated impulse withstand voltage U
imp
V AC 6000
Mechanical shock resistance g 15
Mounting position As required
Contacts
Electrical characteristics
Rated operational voltage U
e
V AC 690
Rated uninterrupted current I
u
A 20
Note on rated uninterrupted current !
u
Rated uninterrupted current I
u
is specified for max. cross-section.
Load rating with intermittent operation, class 12
AB 25 % DF x I
e
2
AB 40 % DF x I
e
1.6
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A gG/gL 20
Rated short-time withstand current (1 s current) I
cw
A
rms
320
Note on rated short-time withstand current lcw Current for a time of 1 second
Rated conditional short-circuit current I
q
kA 6
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 130
Rated breaking capacity cos ϕ to IEC 60947-3 A
230 V A 100
400/415 V A 110
500 V A 80
690 V A 60
Safe isolation to EN 61140
between the contacts V AC 440
Current heat loss per contact at I
e
W 0.6
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 0.6
Lifespan, mechanical Operations
x 10
6
> 0.4
Maximum operating frequency Operations/h 1200
AC
AC-3
Rating, motor load switch P kW
220 V 230 V P kW 3
230 V Star-delta P kW 5.5
400 V 415 V P kW 5.5
400 V Star-delta P kW 7.5
500 V P kW 5.5
500 V Star-delta P kW 7.5
690 V P kW 4
690 V Star-delta P kW 5.5
Rated operational current motor load switch
230 V I
e
A 11.5
230 V star-delta I
e
A 20
400V 415 V I
e
A 11.5
400 V star-delta I
e
A 20
500 V I
e
A 9
500 V star-delta I
e
A 15.6
690 V I
e
A 4.9
690 V star-delta I
e
A 8.5
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 3
06/16/2021 Eaton 009315 ED2021 V80.0 EN 2 / 5