Data Sheet

DATASHEET - 22DILEM
Auxiliary contact module, 4 pole, 2 N/O, 2 NC, Front fixing, Screw
terminals, DILE(E)M
Part no. 22DILEM
Catalog No. 010112
Alternate Catalog
No.
XTMCXFC22
EL-Nummer
(Norway)
4130387
Delivery program
Accessories Auxiliary contact modules
Description with interlocked opposing contacts
Switching elements according to EN 50012
Switching elements according to EN 50012 are to be preferred.
Version E combinations correspond to EN 50011 and are to be preferred.
Function for standard applications
Number of poles 4 pole
Connection technique Screw terminals
Rated operational current
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 2
Contacts
N/O = Normally open 2 N/O
N/C = Normally closed 2 NC
Mounting type Front fixing
Contact sequence
For use with DILEM-10(-G)(…)
DILEM-4(-G)(…)
DILEEM-10(-G)(…)
DILEM12-10(-G)(…)
Instructions Interlocked opposing contacts according to IEC/EN 60947-5-1 appendix L, inside the
auxiliary contact modules, also for the integrated auxiliary contacts of the DILER,
DILE(E)M
Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix
F (not N/C late open)
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations
x 10
6
10
DC operated Operations
x 10
6
20
Component lifespan at U
e
= 240 V
AC-15 Operations
x 10
6
0.2
DC
L/R = 50 ms: 2 contacts in series at I
e
= 0.5 A Operations
x 10
6
0.15
Maximum operating frequency Operations/h 9000
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C - 25 - 40
Ambient temperature, storage °C - 40 - 80
06/16/2021 Eaton 010112 ED2021 V80.0 EN 1 / 5