Data Sheet

DATASHEET - ZE-6
Overload relay, Ir= 4 - 6 A, 1 N/O, 1 N/C, Direct mounting
Part no. ZE-6
Catalog No. 014565
Alternate Catalog
No.
XTOM006AC1
EL-Nummer
(Norway)
4130482
Delivery program
Product range ZE overload relays for mini contactor relays
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
Setting range
Overload releases I
r
A 4 - 6
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILEM
DIULEM/21/MV
Short-circuit protection
Type “1” coordination gG/gL A 35
Type “2” coordination gG/gL A 10
Notes
Overload trigger: tripping class 10 A
Short circuit protection: observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors
II(2)G [Ex d] [Ex e] [Ex px]
II(2)D [Ex p] [Ex t]
PTB 10 ATEX 3014
Observe manual MN03407003Z-DE/EN.
Notes
When fitted directly to the contactor a clearance of at least 5mm is required between the overload relays.