Data Sheet

DC 24 - 240
Rated frequency AC Hz 47 - 63
Tolerance AC operated min. x U
c
0.85
Tolerance AC operated max. x U
c
1.1
Tolerance DC operated min. x U
c
0.7
Tolerance DC operated max. x U
c
1.1
Power consumption
Pick-up AC VA 2
Sealing AC VA 2
Pick-up DC W 1.8
Sealing DC W 1.8
Duty factor % DF 100
Maximum operating frequency Ops/h 4000
Minimum command time
AC ms 50
DC ms 30
Repetition accuracy (deviation) % ≦ 0.5
Recovery time (after 100% time delay) ms 70
Contact changeover time t
u
ms 4
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)
applied standard IEC/EN 61000-4-2
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI)
applied standard IEC/EN 61000-4-3
V/m 80 - 1000 MHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1
Radio interference suppression EN 55011, Class B (conducted)
EN 55011, Class B (radiated)
Burst kV Supply cables: 2
Signal cables: 1
according to IEC/EN 61000-4-4
power pulses (Surge) 2 kV (symmetrical)
4 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 1.4
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 1.8
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
06/16/2021 Eaton 031882 ED2021 V80.0 EN 3 / 6