Data Sheet

400 V star-delta I
e
A 32
500 V I
e
A 23.7
500 V star-delta I
e
A 32
690 V I
e
A 14.7
690 V star-delta I
e
A 25.5
AC-21A
Rated operational current switch
440 V I
e
A 32
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 7.5
400 V 415 V P kW 15
500 V P kW 15
690 V P kW 15
Rated operational current motor load switch
230 V I
e
A 32
400 V 415 V I
e
A 32
500 V I
e
A 26.4
690 V I
e
A 17
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 25
Voltage per contact pair in series V 60
DC-21A I
e
A
Rated operational current I
e
A 1
Contacts Quantity 1
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current I
e
A 25
Contacts Quantity 1
48 V
Rated operational current I
e
A 25
Contacts Quantity 2
60 V
Rated operational current I
e
A 25
Contacts Quantity 3
120 V
Rated operational current I
e
A 12
Contacts Quantity 3
240 V
Rated operational current I
e
A 5
Contacts Quantity 5
DC-13, Control switches L/R = 50 ms
Rated operational current I
e
A 20
Voltage per contact pair in series V 24
Control circuit reliability at 24 V DC, 10 mA Fault
probability
H
F
< 10
-5
, < 1 fault in 100000 operations
Terminal capacities
Solid or stranded
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrules to DIN 46228
mm
2
1 x (0.75 - 4)
2 x (0.75 - 4)
Terminal screw M4
Tightening torque for terminal screw Nm 1.6
01/09/2020 Eaton 036961 ED2019 V63.0 EN 3 / 6