Data Sheet

Technical safety parameters:
Notes B10
d
values as per EN ISO 13849-1, table C1
Rating data for approved types
Contacts
Rated operational voltage U
e
V AC 600
Rated uninterrupted current max.
Main conducting paths
General use A 25
Auxiliary contacts
General Use I
U
A 10
Pilot Duty A 600
Switching capacity
Maximum motor rating
Single-phase
120 V AC HP 1.5
200 V AC HP 3
240 V AC HP 3
Three-phase
200 V AC HP 3
240 V AC HP 3
480 V AC HP 7.5
600 V AC HP 10
Short Circuit Current Rating SCCR
Basic Rating kA 5
max. Fuse A 40
High fault rating kA 10
max. Fuse A 40, Class J
Terminal capacity
Solid or flexible conductor with ferrule AWG 14 - 10
Terminal screw M4
Tightening torque lb-in 17.7
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 32
Heat dissipation per pole, current-dependent P
vid
W 1.1
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation UV resistance only in connection with protective shield.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
01/09/2020 Eaton 036961 ED2019 V63.0 EN 4 / 6