Data Sheet
1 x M50/32
6 x M25/16
Technical data
General
Standards EN 62208
EN 61439-2
Ambient temperature °C -40 - +80
Degree of Protection IP65
Material characteristics
Material glass-fibre reinforced polycarbonate (base)
non-reinforced polycarbonate (cover)
Halogen free
Surface treatment Resistant to corrosion
Material properties
Thermal
Temperature resistant -40 °C - 120 °C (enclosure)
85 °C (enclosure bolt)
80 °C (gasket)
Chemical resistance
Chemical resistant Resistant against: Acids < 10 %, mineral oil, alcohol, gasoline, greases, salt
solutions
Partly resistant to: Acids > 10 %
Not resistant to: alkalis, benzene
Atmospheric
Saline spray IEC 60068-2-11
UV resistance Beneath protective shield
Flammability characteristics
Flammability classification according to UL94 V1 (base)
V2 (cover)
Design verification as per IEC/EN 61439
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 22
Starting enclosure for wall mounting P
V
W 21
Middle enclosure for wall mounting P
V
W 20
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 44
Starting enclosure for wall mounting P
V
W 42
Middle enclosure for wall mounting P
V
W 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Not relevant to indoor installations.
10.2.5 Lifting 10 kg per enclosure with support frame and lifting aid met; assembled and secured
as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact IK10
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES IP65
10.4 Clearances and creepage distances Is the panel builder's responsibility.
10.5 Protection against electric shock Protection class 2, therefore not applicable.
06/16/2021 Eaton 095506 ED2021 V80.0 EN 2 / 4