Data Sheet

Conversion time, analog/digital ms each CPU cycle
Relay outputs
Outputs in groups of 1
Parallel switching of outputs for increased output Not permissible
Protection of an output relay Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation from power supply: yes
From the inputs: yes
in groups
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC
Lifespan, mechanical Operations
x 10
6
10
Contacts
Conventional thermal current (10 A UL) A 8
Recommended for load: 12 V AC/DC mA > 500
Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A A 16
Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A A 16
Rated impulse withstand voltage U
imp
of contact coil kV 6
Rated operational voltage U
e
V AC 250
Rated insulation voltage U
i
V AC 250
Safe isolation according to EN 50178 V AC 300 between coil and contact
300 between two contacts
Making capacity
AC–-15, 250 V AC, 3 A (600 ops./h) Operations 300000
DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) Operations 200000
Breaking capacity
AC-15, 250 V AC, 3 A (600 Ops./h) Operations 300000
DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) Operations 200000
Filament bulb load
1000 W at 230/240 V AC Operations 25000
500 W at 115/120 V AC Operations 25000
Fluorescent lamp load
Fluorescent lamp load 10 x 58 W at 230/240 V AC
With upstream electrical device Operations 25000
Uncompensated Operations 25000
Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated Operations 25000
Switching frequency
Mechanical operations
x 10
6
10
Switching frequency Hz 10
Resistive load/lamp load Hz 2
Inductive load Hz 0.5
UL/CSA
Uninterrupted current at 240 V AC A 10
Uninterrupted current at 24 V DC A 8
AC
Control Circuit Rating Codes (utilization category) B 300 Light Pilot Duty
Max. rated operational voltage V AC 300
max. thermal continuous current cos ϕ = 1 at B 300 A 5
max. make/break cos ϕ ≠ capacity 1 at B 300 VA 3600/360
DC
Control Circuit Rating Codes (utilization category) R 300 Light Pilot Duty
Max. rated operational voltage V DC 300
Max. thermal uninterrupted current at R 300 A 1
Max. make/break capacity at R 300 VA 28/28
Network easyNet
Bus termination (first and last station) EASY-NT-R plug (incl. bus terminating resistor 120 Ω)
06/18/2021 Eaton 106406 ED2021 V80.0 EN 4 / 6