Data Sheet

DATASHEET - EC4E-221-6D4T1
I/O expansion, integrated, 24 V DC, 6DI, 4DO(T)
Part no. EC4E-221-6D4T1
Catalog No. 114297
EL-Nummer
(Norway)
4560854
Delivery program
Product range Remote I/O systems
Compact PLCs
Subrange I/O expansions digital/analog
Basic function Expansions
Description usable via CANopen®
Function CANopen® expansion EC4E
Inputs
Inputs expansion (number) Digital: 6
Outputs
Transistor 4
Additional features
Real time clock #
Supply voltage 24 V DC
For use with easy800
EC4P
MFD-CP8…
MFD-CP10...
For use with XC100/200, EC4P, MFD4 (via CANopen®)
Technical data
General
Dimensions (W x H x D) mm 71.5 x 90 x 58 (4 PE)
Weight kg 0.2
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Terminal capacities
Solid
mm
2
0.2/4 (AWG 22 - 12)
Flexible with ferrule
mm
2
0.2/2.5 (AWG 22 - 12)
Standard screwdriver mm 0.8 x 3.5
Max. tightening torque Nm 0.6
Climatic environmental conditions
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Condensation Take appropriate measures to prevent condensation
Storage ϑ °C -40 - +70
Ambient conditions, mechanical
Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree II/2
Electrostatic discharge (ESD)
applied standard IEC/EN 61000-4-2, Level 3
Air discharge kV 8
Electromagnetic fields (RFI) to IEC EN 61000-4-3 V/m 10
Burst kV according to IEC/EN 61000-4-4
power pulses (Surge) 2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance EN 50178
06/16/2021 Eaton 114297 ED2021 V80.0 EN 1 / 4

Summary of content (4 pages)