Data Sheet

Material Housing: polyamide PA not reinforced
Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Duty factor % DF 100
Operating conditions
Climatic environmental conditions
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Ambient temperature
Operation ϑ °C -20 - +55
Storage ϑ °C -40 - +70
Condensation Non-condensing
Atmospheric conditions
relative humidity % Max. 75
Air pressure (operation) hPa 795 - 1080
Altitude Above sea
level
m 2000
Power loss P W 4.52
Ambient conditions, mechanical
Degree of protection to VDE 0470-1
Enclosures IP20
Terminals IP20
Degree of Protection Installation location: ≥ IP54
B10d [switching cycles] 300000
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Vibrations (IEC/EN 60068-2-6) 10 - 150 Hz
Amplitude: 0.15 mm
Acceleration: 2 g
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 14-95
Rated impulse withstand voltage U
imp
V AC 4000
Insulation Basic isolation
Safe isolation, reinforced isolation, and 6 kV between input circuit / NC contacts,
and enable current paths.
Overvoltage category/pollution degree III/2
Stop category according to
EN60204-1
13,5
Technical safety parameters:
Values according to EN ISO 13849-1
Performance level according
to EN ISO
13849-1
PL d
Category according
to EN ISO
13849-1
Kat. 3
Safety integrity level claim limit in accordance
with 62061
SILCL 3
Safety integrity level In
accordance
with IEC 61508
SIL 3
Probability of failure per hour PFH
d
x 10
-10
13.5
Prooftest High Demand Months 240
Prooftest Low Demand Months 67
Rated operational voltage U
e
V AC 230
Rated operational voltage U
e
V 24 V DC
Permissible range 0.85 - 1.1 x Ue
Rated insulation voltage U
i
V AC 250
Quadratic summation current
A
2
50 A
2
(I
TH
2
= I
1
2
+ I
2
2
+ I
3
2
+ I
4
2
)
Notes Observe derating curve
→ Engineering
Inrush current A min - max 0.025 - 6 (N/O) 0.025 - 3 (N/C)
Minimum switching capacity W 0.4
Control circuit
Power supply circuit
06/16/2021 Eaton 118706 ED2021 V80.0 EN 2 / 6