Data Sheet

Control circuit
Power supply circuit
AC operated 50/60 Hz W 5.8
DC operated W 2.9
Fuse for control circuit supply
115 V/230 V short-circuit proof
Input data
Rated current mA S10, S12, S22:35, S34, S35:45
Current consumption mA AC: 22
Voltage at input, starting and feedback circuit V DC Approx. 24
Max. resistive load of the cable R ≦ 11
Short-circuit current A 0.7
Pick-up time (K1, K2) for UN automatic mode, typical t
A
ms 300
Pick-up time (K1, K2) for UN manual operation, typical t
A
ms 40
Pick-up time ms at Ue in automatic mode: normally 300
at Ue in manual mode: normally 40
Typical pick-up time 330 ms (if actuated via A1)
Reset time (K1, K2) for U
N
, normally t
R
ms 150 (single-channel)
20 (two-channel)
Recovery time t
W
ms Approx. 1000
Simultaneity for inputs 1/2 t
sync
ms
Maximum permissible total cable resistance (input and starting circuits for UN) R
L
Ω 50
Maximum switching frequency Hz 0.5
Status indication Green LED
Output data
Contact type
Non-delayed enable current paths 3
Delayed signal current path 1
Switching voltage min – max 10 - 250 V AC
10 - 250 V DC
Limiting continuous current A per N/O: 6
N/C: 5
Short-circuit protection for output circuits, external Fuse 10 A gL/gG (Enable current paths)
Fuse 4 A gL/gG (Signal current paths)
Output fuse
NEOZED (N/O) gL/gG 10
NEOZED (N/C) gL/gG 6
Maximum breaking power
Resistive load (τ = 0 ms)
24 V DC W 144
48 V DC W 230
110 V DC W 68
220 V DC W 88
250 V AC VA 2000
Inductive load (τ = 40 ms)
24 V DC W 48
48 V DC W 40
110 V DC W 35
220 V DC W 33
Switching capacity
In accordance with IEC 60947-5-1
AC-15
230 V A 5 A bei 3600S/h
DC-13
24 V A 5 A bei 3600S/h
Further information (flip catalog) description
Electromagnetic compatibility (EMC)
Emitted interference In accordance with EN 61000-6-4
06/16/2021 Eaton 119380 ED2021 V80.0 EN 3 / 6