Data Sheet

DATASHEET - SOL30-SAFETY/2MC4-U(230V50HZ)
Fireman's switch, 30A, MC4, UA 230V50Hz
Part no. SOL30-SAFETY/2MC4-U(230V50HZ)
Catalog No. 144122
Alternate Catalog
No.
SOL30-SAFETY-2MC4-UF
EL-Nummer
(Norway)
4300325
Delivery program
Product range Switchgear for photovoltaic systems
Subrange Fireman's switch
Product range Fireman's Switch
Application field Residential buildings
Utility buildings
Part no. SOL-Safety
Rated operational voltage U
e
V 1000
Rated operational current at DC-21A I
e
A 30
Rated operational current at DC-PV1 I
e
A 30
Rated operational current at DC-PV2 I
e
A 10
Inputs number of strings 2
Inputs connection type MC4
Outputs number of strings 1
Outputs connection type MC4
Technical data
General
Standards IEC/EN 60947-3
Mounting position
Description Application: DC isolation in photovoltaic systems between PV generator and power
inverter for disconnecting power
Remote tripping with integrated undervoltage release 230 V, 50 Hz
Signalling of switch state via auxiliary contact 1 N/O and 1 NC
Prewired ready for connection
Lockable with padlock in OFF position
Spring switch function
Electrical
Number of poles 2 pole
Rated operational voltage U
e
V 1000
Rated operational current at DC-21A I
e
A 30
Rated operational current at DC-PV1 I
e
A 30
Rated operational current at DC-PV2 I
e
A 10
Rated short-time withstand current (t=1s) I
cw
kA 0.7
up to 440 V 50/60 Hz I
cm
kA 0.3
Utilization category DC-21 A
DC-PV1
DC-PV2
Overvoltage category/pollution degree III/3
Rated impulse withstand voltage U
imp
kV 8
Electrical Operations1500
Internal resistance mΩ 7
Mechanical
Weight kg 0.47
Degree of Protection IP65
Ambient temperature
Open °C -25 - +60
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
06/18/2021 Eaton 144122 ED2021 V80.0 EN 1 / 4