Data Sheet

DATASHEET - FRCDM-40/4/003-G/B+
Digital residual current circuit-breaker, all-current sensitive, 40 A, 4p, 30
mA, type G/B+
Part no. FRCDM-40/4/003-G/B+
Catalog No. 167881
Alternate Catalog
No.
FRCDM-40/4/003-G/B.
EL-Nummer
(Norway)
0001664172
Delivery program
Basic function Residual current circuit-breakers , digital
Number of poles 4 pole
Application Switchgear for industrial and advanced commercial applications
Rated current I
n
A 40
Rated short-circuit strength I
cn
kA 10
Rated fault current I
ΔN
A 0.03
Type Type G/B+ (ÖVE E 8601)
Tripping s… Short time-delayed
Product range FRCdM
Sensitivity All current sensitive
Impulse withstand current Surge-proof, 3 kA
Contact sequence
Technical data
Electrical
Types conform to VDE 0664-400
ÖVE E 8601
Standards IEC/EN 61008
EN 45545-2; IEC 61373
Current test marks As per inscription
Tripping s… 10 ms delayed
Rated voltage according to IEC/EN 60947-2 U
n
V AC 240/415
Rated frequency f Hz 50
Limit values of the operating voltage
electronic V AC 50 - 456
Test circuit V AC 196 - 264
Rated fault current I
Δn
mA 30
Sensitivity All current sensitive
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4
Rated short-circuit strength I
cn
kA 10
Impulse withstand current 3 kA (8/20 μs) surge-proof
Max. admissible back-up fuse
Short-circuit gG/gL A 63
Overload gG/gL A 40
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 500
lifespan
Electrical Operations ≧ 4000
Mechanical Operations ≧ 20000
06/18/2021 Eaton 167881 ED2021 V80.0 EN 1 / 5

Summary of content (5 pages)