Data Sheet

Mechanical Operations ≧ 20000
Dry auxiliary contact
Rated switching capacity
30 VDC (resistive load) A 2
240 VAC (resistive load) A 0.25
Max. switching duty (resistive load) W 60
Max. switching voltage AC V 240
Max. switching voltage DC V 220
Maximum switching current A 2
Min. switching capacity (reference value) 10 μA, 10 mV DC
lifespan
Electrical (at 20 switching operations per minute) 2 A 30 VDC resistive load Operations
>10
5
Electrical (at 20 switching operations per minute) 1 A 30 VDC resistive load Operations
>5 x 10
5
Terminal capacity mm² 0.25 - 1.5
Mechanical
Standard front dimension mm 45
Device height mm 80
Built-in width mm 70 (4TE)
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP20, IP40 with suitable enclosure
Terminals top and bottom Twin-purpose terminals
Terminal protection finger and hand touch safe, DGUV VS3, EN 50274
Terminal cross-section
Solid
mm
2
1.5 - 35
Stranded
mm
2
2 x 16
Terminal cross-section M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2)
Tightening torque of fixing screws N/m 2 - 2.4
Thickness of busbar material mm 0.8 - 2
Admissible ambient temperature range °C -25 - +60
Permissible storage and transport temperatures °C -35 - +60
Climatic proofing 25-55°C/90-95% relative humidity according to IEC 60068-2
Mounting position As required
Contact position indicator red / green
Trip indication white / blue
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 63
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 10
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
Maximum operating temperature is 60 °C in accordance with the de-rating table
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
06/18/2021 Eaton 167894 ED2021 V80.0 EN 2 / 5