4 Operation
4.5 Handling the keypad
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 121
4.5.4 Extended parameter set
Table 17: Enabling and disabling access to the extended parameter set
Commands
Description
Enabling access to the extended parameter set
Press the OK button and hold it down for two seconds in
order to access the parameter interface
The display will show the parameter that was last used.
Use the and buttons to select parameter P-14
Press the OK button.
Use the and buttons to enter the password set with
P-37 (default setting: 101)
Press the OK button to confirm
The extended parameter set (parameters > P-14 and
display values P00-…) will now be available.
Disabling access to the extended parameter set
Use the and buttons to set a value for P-14 that
does not match the password (P-37).
Press the OK button to confirm
Only the “basic parameters”, P-01 to P-14, will be
accessible now.
The extended parameter set (default setting for P-37 = 101)
contains parameters P-01 to P-59.
Additional parameters P-60 to P-68 can be configured for
specific applications. The corresponding password is 201 in
parameter P-37 (value of P-37 + 100).