User manual

1 DC1 device series
1.7 Selection criteria
DC1 Variable Frequency Drive 04/16 MN04020003Z-EN www.eaton.com 27
1.7 Selection criteria
Select the variable frequency drive according to the supply voltage U
LN
of
the supply system and the rated operational current of the assigned motor.
The circuit type ( / ) of the motor must be selected according to the
supply voltage.
The variable frequency drive’s rated output current I
e
must be greater than or
equal to the rated motor current.
Figure 12: Selection criteria
When selecting the drive, the following criteria must be known:
Mains voltage = rated operating voltage of the motor (e. g. 3~ 400 V),
Type of motor (e.g., three-phase asynchronous motor)
Rated motor current (recommended value, dependent on the circuit type
and the power supply)
Ambient conditions: ambient temperature, control cabinet installation
with IP20 degree of protection or direct local installation with IP66
degree of protection.
Example based on figure 12
Mains voltage: 3~ 400 V, 50 Hz
Star-connected circuit (400 V)
Rated operational current: 1.9 A (400 V)
Control panel installation
IP20 degree of protection
Ambient air temperature max. 50 °C without output reduction, IP20
Variable frequency drive that should be selected: DC1-342D2FN-A20N
DC1-34…: 3-phase main terminal, rated operating voltage: 400 V
DC1-…2D2…: 2.2 A – The variable frequency drive’s rated operational
current (output current) guarantees that the motor will be supplied with
the required rated operational current (1.9 A).
1410 min
230/400 V 3.2/1.9 A
50 Hz
-1
0,75 KW
cos ϕ 0.79
P-07
P-08
P-10
P-09
L1/L
L2/N
L3
U
V
W
1
2
3
4
5
6
7
8
9
10
11