DC1 Variable Frequency Drives 11/16 MN04020004Z-EN www.eaton.com 29
4 Messages
4.1 List of messages
Table 22: Messages
Message
Possible causes and fixes
STOP Ready to start. There is no drive enable signal present. There are no fault messages present.
P-dEf The parameters‘ default settings have been loaded.
O-I Overcurrent at variable frequency drive output
Occurs right after switching on the unit:
Check the cable connection between the variable frequency drive and the motor
Check the motor for shorted turns and ground faults
Occurs when starting the motor:
Check whether the motor can rotate freely and make sure that it is not being blocked mechanically.
Motor with mechanical brake: Check whether the brake is being applied.
Check the connection configuration (star/delta)
Check to make sure that the correct rated motor current has been entered in P-08
Increase the acceleration ramp time (t-acc, P-03) if necessary.
Reduce the voltage boost with P-11.
Occurs during operation at a constant speed:
Check whether the motor is overloaded.
Occurs during acceleration/deceleration:
The ramp times are too short and require too much power.
If P-03 / P-04 cannot be increased, a larger device may be required.
I.t-trP
Motor overload. The thermal protection mechanism has tripped as a result of the device being run above the rated
motor current set with P-08 longer than a specific time.
Check to make sure that the rated motor current has been entered in P-08.
Check the motor's connection configuration (e.g., start/delta)
If the decimal points on the display flash during operation, this means that the unit is being run in its overload
range (> P-08). In this case, use P-03 to make the acceleration ramp longer or reduce the load.
Check whether the motor is being blocked mechanically or whether there are any additional loads.
OI-b
Excessively high braking current
Check the brake resistor and its wiring for short-circuits and ground faults.
Make sure that the braking resistance value is not lower than the minimum permissible braking resistance.
OL-br Thermal overload on brake resistor. The drive has been switched off in order to prevent the brake resistor from being
thermally destroyed. This message will only be output if P-34 = 1 ("braking chopper")
Make the P-04 and P-24 ramp times longer in order to have less frequent braking.
Reduce the load's inertia (if possible).
If the protection achieved with P-34 = 1 is not adequate for the brake resistor being used:
Provide external protection for the brake resistor and set P-34 to a value of 2.
PS-trp
Overcurrent (Hardware)
Check the wiring to the motor and the motor itself for short-circuits and ground faults.
Disconnect the motor cable from the variable frequency drive and switch the variable frequency drive back on.
If the fault message still appears, the device needs to be replaced. Before commissioning the new device, check
the system for short-circuits or ground faults that could have caused the device to fail.
O.Volt
Overvoltage in DC link
Check to make sure that the supply voltage falls within the range for which the variable frequency drive is sized.
If the error occurs during deceleration or stopping:
Make the deceleration ramp (P-04/P-24) longer or use the brake resistor and activate the braking chopper with
P-34 (only on devices with frame size FS2, FS3, or FS4).