Frequenzumrichter 9000X
SVX, SPX
CA04020001Z-DE-INT www.eaton.eu
77
SVX/SPX
SVX, SPX
Typschlüssel
Information relevant for export to North America
Product Standards UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No. E134360
UL Category Control No. NMMS, NMMS2, NMMS7. NMMS8
CSA File No. UL report applies to both US and Canada
CSA Class No. 3211-06
North America Certification UL listed, certified by UL for use in Canada
Specially designed for North
America
No
Suitable for Branch circuits
Max. Voltage Rating
SVX/SPX…-4… 3~ 480 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
SVX/SPX…-5… 3~ 690 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
Degree of Protection
SPX…A0… IEC: IP00
SVX/SPX…A1… IEC: IP21
SVX/SPX…A2… IEC: IP54
SVX 007 A 1 - 4 A 1 B 1...
0 = IP00/open chassis
1 = IP21/NEMA 1
2 = IP54/NEMA 12
F07 = 0.75 HP = 0.55 kW
001 = 1 HP = 0.75 kW
...
007 = 7.5 HP = 5.5 kW
...
H20 = 2000 HP = 1800 kW
4 = 380 V (-15 %) - 500 V (+10 %)
5 = 525 V (-15 %) - 690 V (+10 %)
2 = 208 V (-15 %) - 240 V (+10 %)
AFD Software-Serie
A = Standardversion
zugeordnete Motorleistung
gemäß Netzspannungsklasse 4, 5
Gerätereihe
SVX = Standardfrequenzumrichter
SPX = Performance Frequenzumrichter
Schutzart
Ausführung
1 = Standardbaugruppen
Auf Anfrage:
2 = zusätzlicher Platinenschutz
U = 12-Puls-Schaltung
V = 12-Puls-Schaltung mit DC-Kopplung
Brems-Chopper
N = kein interner Brems-Chopper
B = interner Brems-Chopper
Netzspannungsklasse
Anzeigeeinheit (Display)
A = alphanummerisch
EMV-Funkentstörfilter
1 = Kategorie C2 in 1. und 2. Umgebung
2 = kein interner RFI-Filter
4 = Kategorie C3 in 2. Umgebung
Auf Anfrage:
UL/CSA