Data Sheet

10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Motor starter/Motor starter combination (EC001037)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Motor starter combination (ecl@ss10.0.1-27-37-09-05
[AJZ718013])
Kind of motor starter Direct starter
With short-circuit release No
Rated control supply voltage Us at AC 50HZ V 0 - 0
Rated control supply voltage Us at AC 60HZ V 0 - 0
Rated control supply voltage Us at DC V 24 - 24
Voltage type for actuating DC
Rated operation power at AC-3, 230 V, 3-phase kW 1.5
Rated operation power at AC-3, 400 V kW 3
Rated power, 460 V, 60 Hz, 3-phase kW 0
Rated power, 575 V, 60 Hz, 3-phase kW 0
Rated operation current Ie A 9
Rated operation current at AC-3, 400 V A 6.5
Overload release current setting A 1.5 - 9
Rated conditional short-circuit current, type 1, 480 Y/277 V A 0
Rated conditional short-circuit current, type 1, 600 Y/347 V A 0
Rated conditional short-circuit current, type 2, 230 V A 0
Rated conditional short-circuit current, type 2, 400 V A 0
Number of auxiliary contacts as normally open contact 1
Number of auxiliary contacts as normally closed contact 1
Ambient temperature, upper operating limit °C 40
Temperature compensated overload protection Yes
Release class CLASS 10
Type of electrical connection of main circuit Screw connection
Type of electrical connection for auxiliary- and control current circuit Screw connection
Rail mounting possible Yes
With transformer No
Number of command positions
Suitable for emergency stop No
Coordination class according to IEC 60947-4-3
Number of indicator lights 3
External reset possible Yes
With fuse No
Degree of protection (IP) IP20
Degree of protection (NEMA) Other
Supporting protocol for TCP/IP No
06/16/2021 Eaton Y7-197164 ED2021 V80.0 EN 3 / 6