Data Sheet

Input current mA < 1
Cable length m ≦ 30, screened
Transistor outputs
Number 4
Rated operational voltage U
e
V DC 24
Permissible range U
e
20.4 - 28.8 V DC
Residual ripple % 5
Supply current mA Norm./max. 15
Protection against polarity reversal Yes (Caution: A short circuit will occur if a supply voltage of the wrong polarity is
applied to the outputs.)
Potential isolation from power supply: yes
to the memory card: yes
to Ethernet: yes
From the inputs: yes
to control buttons: yes
between the outputs: no
to expansion devices: yes
Rated operational current at signal „1” DC per channel I
e
A Max. 0.5
Residual current on 0 signal per channel mA < 0.005
Max. output voltage V 1 (at status 0 per channel)
U = U
e
- 1 V (signal 1 at I
e
= 0.5 A)
Short-circuit protection yes, electronic (Q1 - Q4)
Short-circuit tripping current for R
a
≦ 10 mΩ A 0.7 ≦ I
e
≦ 1.7 per output
depending on number of active channels and their load
Total short-circuit current A 6.8
Thermal cutout Yes
Max. operating frequency with constant resistive load Operations/
h
abhängig von der Zykluszeit des Basisgeräts und bei Erweiterungsgeräten auch
von deren Übertragungszeit
Parallel connection of outputs
With resistive load, inductive load with external suppressor circuit,
combination within a group
Group 1: Q1 to Q4
Number of outputs max. 4
Max. total current A 2
Inductive load to EN 60947-5-1
Without external suppressor circuit
DC-13, T
0.95 = 72 ms, R = 48 Ω, L = 1.15 H
Utilization factor g 0.25
Duty factor % DF 100
T
0.95 = 15 ms, R = 48 Ω, L = 0.24 H
Utilization factor g 0.25
Duty factor % DF 100
With external suppressor circuit
Utilization factor g 1
Duty factor % DF 100
Max. switching frequency, max. duty factor OperationsDepending on the suppressor circuit
Ethernet
Data transfer rate Mbit/s 10/100
Connections RJ45 plug, 8-pin
Cable CAT5
Design verification as per IEC/EN 61439
Technical data for design verification
Static heat dissipation, non-current-dependent P
vs
W 2
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
06/18/2021 Eaton Y7-197507 ED2021 V80.0 EN 4 / 7