Owner`s manual

31
Section 9 Quick Reference Guide
Problem LED Things to Check Active Alarm Solution
Unit running in AUTO but no
power in house.
GREEN Check MLCB. NONE Check MLCB. If it is in the ON position, contact the
servicing dealer.
Unit shuts down during
operation.
RED Check the LEDs / Screen for
alarms.
HIGH TEMPERATURE Check ventilation around the generator, intake, exhaust
and rear of generator. If no obstruction, contact serving
dealer.
Unit shuts down during
operation.
RED Check the LEDs / Screen for
alarms.
OVERLOAD REMOVE
LOAD
Clear alarm and remove household loads from the
generator. Put back in AUTO and restart.
Unit was running and shuts
down, attempts to restart.
RED check the LEDs / Screen for
alarms.
RPM SENSE LOSS Clear alarm and remove household loads from the
generator. Put back in AUTO and restart. If this does not
work, contact the servicing dealer.
Unit will not start in AUTO with
utility loss.
NONE See if screen says unit not
activated.
NOT ACTIVATED Refer to activation section in Owner’s Manual.
Unit will not start in AUTO with
utility loss.
GREEN Check screen for start delay
countdown.
None If the start up delay is greater than expected, contact
servicing dealer to adjust from 2 to 1500 seconds.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
LOW OIL PRESSURE Check oil level / Add oil per Owner’s Manual. If oil level
is correct, contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
RPM SENSE LOSS Clear alarm. Using the control panel, check the battery
by navigating to the BATTERY MENU option from the
MAIN MENU. If it states battery is GOOD, contact
servicing dealer. If it states CHECK BATTERY, replace
the battery.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
OVERCRANK Check fuel line shutoff valve is in the ON position. Clear
alarm. Attempt to start the unit in MANUAL. If it does not
start or starts and runs rough, contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
LOW VOLTS REMOVE
LOAD
Clear alarm and remove household loads from the
generator. Put back in AUTO and restart.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
FUSE PROBLEM Check the 7.5amp fuse. If it is bad, replace it with an
ATO 7.5Amp fuse, if not, contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
OVERSPEED Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
UNDERVOLTAGE Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
UNDERSPEED Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
STEPPER
OVERCURRENT
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
MISWIRE Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED Check the LEDs / Screen for
alarms.
OVERVOLTAGE Contact servicing dealer.
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
LOW BATTERY Clear alarm. Using the control panel, check the battery
by navigating to the BATTERY MENU option from the
MAIN MENU.. If it states battery is GOOD, contact
servicing dealer. If it states CHECK BATTERY, replace
the battery.
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
BATTERY PROBLEM Contact servicing dealer.
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
CHARGER WARNING Contact servicing dealer
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
SERVICE A Perform SERVICE A maintenance. Press ENTER to
clear.
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
SERVICE B Perform SERVICE B maintenance. Press ENTER to
clear.
Yellow LED illuminated in any
state.
YELLOW Check the screen for
additional information.
Inspect Battery Inspect Battery. Press ENTER to clear.