Information

Table Of Contents
1/132 Motoren schalten und schützen CA034001DE – Dezember 2017 www.eaton.eu
Leistungsschütze
DILM185A – DILM1600, DILH
1.18
Moeller series
1
DILM185A DILM225A DILM250 DILM300A DILM400 DILM500 DILM580 DILM650 DILM750 DILM820 DILM1000 DILM1600 DILH1200 DILH1400 DILH2000 DILH2200 DILH2600
Approbierte Leistungsdaten
Schaltvermögen
maximale Motorleistung
3-phasig
200 V, 208 V HP 50 60 75 100 125 150
200 200 250 290 560
230 V, 240 V HP 60 75 100 125 150 200 200 250 300 350 400 640
460 V, 480 V HP 125 150 200 250 300 400 400 500 600 700 800 1200
575 V, 600 V HP 150 200 250 300 400 500 600 600 700 860 1000 1300
General use A 250 250 350 350 450 550 980 1041 1102 1225 1225 1600 1380 1600 2000 2200 2600
Hilfsschalter
Pilot Duty
AC-betätigt A600 A600 A600 A600 A600 A600
A600 A600 A600 A600 A600 A600 A600 A600 A600 A600 A600
DC-betätigt P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300 P300
General Use
AC V 600 600 600 600 600 600
600 600 600 600 600 600 600 600 600 600 600
AC A 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
DC V 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250
DC A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Short Circuit Current Rating (SCCR)
Basic Rating
SCCR kA 10 10 18 18 30 30
30 30 42 42 85 85
max. Fuse A 700 700 700 700 800 800 2000 2000 2000 2000 2000 2000
max. CB A 800 600 600 600 600 600 1200 1200 1200 1200 1200
480 V High Fault
SCCR (fuse) kA 100 100 18 18 30/100 30/100
85 85 85 85 85 85
max. Fuse A 600 Class J 600 Class J 700 Class L 700 Class L 800/600 Class J 800/600 Class J 2000 2000 2000 2000 2000 2000
SCCR (CB) kA 65 65 65 65 100 100 85 85 85 85 85
max. CB A 350 350 250 250 600 600 1200 1200 1200 1200 1200
600 V High Fault
SCCR (fuse) kA 100 100 18 18 30/100 30/100
85 85 85 85 85 85
max. Fuse A 600 Class J 600 Class J 700 Class J 700 Class J 800/600 Class J 800/600 Class J 2000 2000 2000 2000 2000 2000
SCCR (CB) kA 50 50 18 18 30 30 85 85 85 85 85
max. CB A 350 350 600 600 600 600 1200 1200 1200 1200 1200
Special Purpose Ratings
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A
1380 1400 2000 2200 2600
600V 60Hz 3phase, 347V 60Hz 1phase A 1380 1400 2000 2200 2600
Refrigeration Control (CSA only) A
Denite Purpose Ratings (100,000 cycles
acc. to UL 1995)
LRA 480V 60Hz 3phase A 2016 2016 2050 2160 3300 3900
4020 4350 4800 5400 6000
FLA 480V 60Hz 3phase A 336 336 300 360 550 635 670 725 800 900 1200
LRA 600V 60Hz 3phase A 1680 1680 1800 1800 3120 3120 4020 4350 4800 5400 6000
FLA 600V 60Hz 3phase A 280 280 250 300 420 520 670 725 800 900 1200