Data Sheet

Flammability characteristics
Glow wire test
Flammability characteristics 960 °C/1mm thickness (base, cover; glow wire to VDE 0471 Part 2)
650 °C/1mm thick (push-through membrane) to VDE 0471 Part 2)
to UL 94 VO/1.5 mm thickness
to UL 94 HB
Halogen free Yes
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 0
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 25.5
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
Degree of Protection Front IP65
IP65, with push-through cable entry
Max. radiated heat dissipation with separate mounting, ambient air
temperature +20 °C
W 25.5
Flammability characteristics 960 °C/1mm thickness (base, cover; glow wire to VDE 0471 Part 2)
650 °C/1mm thick (push-through membrane) to VDE 0471 Part 2)
Track resistance CTI 175 (base, to IEC 60112)
CTI 175 (cover, to IEC 60112)
Surface treatment Resistant to corrosion
Impact resistance IK06 according to EN 50102
Temperature resistant -40 °C - 120 °C (enclosure)
-40 °C - +80 °C (gasket)
UV resistance Beneath protective shield
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Please enquire
10.2.5 Lifting Not applicable.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Meets the product standard's requirements.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.