BUSSMANN Technical Data 10164 Effective September 2015 Supersedes February 2015 SERIES Bussmann series 500 Volts gG/gL NH Fuse links Product description Eaton’s Bussmann series 500 Volts NH square bodied industrial fuse links are suitable for a wide variety of applications.
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Catalogue symbol: Fuse holders (ordered separately) (amp)NHG(size)B • • Fuse size: • 000 to 4 • Fuse bases: • DIN-Rail mounting and screw mounting: 1-pole SD(size)-D, 3-pole TD(size)-D Technical data: • Volts: 500 V a.c.
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Table 2. Part numbers sizes 000 to 01 Size 000 000 000 000 000 000 000 000 000 000 000 000 000 000 00 00 00 00 00 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 01 01 01 01 01 01 01 01 01 01 01 01 01 01 Rated current (Amps) Rated voltage (V a.c.
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Table 3. Part numbers sizes 1 to 4 Size 1 1 1 1 1 1 1 1 1 1 1 02 02 02 02 02 02 02 02 02 02 02 2 2 2 2 2 2 2 2 03 03 03 03 3 3 3 3 3 3 3 4** 4** 4** 4** 4** Rated current (Amps) Rated voltage (V a.c.
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Time in seconds (s) Time-current curves - NH Size 000 Current in Amps (A) Technical data - NH size 000 Part numbers with metal gripping lugs 2NHG000B 4NHG000B 6NHG000B 10NHG000B 16NHG000B 20NHG000B 25NHG000B 32NHG000B 35NHG000B 40NHG000B 50NHG000B 63NHG000B 80NHG000B 100NHG000B Part numbers with insulated metal gripping lugs 2NHG000BI 4NHG000BI 6NHG000BI 10NHG000BI 16NHG000BI 20NHG000BI 25NHG000BI 32NHG000BI 3
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Time in seconds (s) Time-current curves - NH Size 00 Current in Amps (A) Technical data - NH size 00 Part numbers with metal gripping lugs 50NHG00B 63NHG00B 80NHG00B 100NHG00B 125NHG00B 160NHG00B Part numbers with insulated metal gripping lugs 50NHG00BI** 63NHG00BI** 80NHG00BI** 100NHG00BI** 125NHG00BI 160NHG00BI I2t (Amps2 Seconds) Fuse link size 00 Rated current (Amps) 50 63 80 100 125 160 Rated voltage
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Time-current curves - NH Size 0 10 000 160 125 6 4 100 2 1 000 6 4 80 2 63 50 100 40 6 35 Time in seconds (s) TIME (Seconds) 4 32 25 20 2 10 16 6 10 4 2 1 6 4 2 6 0.1 6 4 2 0.
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Time-current curves - NH Size 01 10 000 6 4 2 1 000 6 160 4 125 100 2 80 100 63 6 50 40 Time in seconds (s) TIME (Seconds) 4 35 2 32 10 25 6 4 2 1 20 6 16 4 10 2 0.1 6 6 4 2 0.
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Time in seconds (s) Time-current curves - NH Size 1 Current in Amps (A) Technical data - NH size 1 Part numbers with metal gripping lugs 50NHG1B Part numbers with insulated metal gripping lugs 50NHG1BI** 63NHG1B 80NHG1B 100NHG1B 125NHG1B 160NHG1B 200NHG1B 224NHG1B 250NHG1B 315NHG1B 355NHG1B I2t (Amps2 Seconds) Rated current (Amps) 50 Rated voltage (V a.c.) 500 Minimum pre-arcing 6350 *I1 120kA at 500 V a.
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Time in seconds (s) Time-current curves - NH Size 02 Current in Amps (A) Technical data - NH size 02 Part numbers with metal gripping lugs 35NHG02B 40NHG02B 50NHG02B Part numbers with insulated metal gripping lugs 35NHG02BI 40NHG02BI 50NHG02BI 63NHG02B 80NHG02B 100NHG02B 125NHG02B 160NHG02B 200NHG02B 224NHG02B 250NHG02B 63NHG02BI 80NHG02BI 100NHG02BI 125NHG02BI 160NHG02BI 200NHG02BI 224NHG02BI 250NHG02BI I
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Time in seconds (s) Time-current curves - NH Size 2 Current in Amps (A) Technical data - NH size 2 Part numbers with metal gripping lugs 250NHG2B 300NHG2B 315NHG2B Part numbers with insulated metal gripping lugs 250NHG2BI** 300NHG1BI** 315NHG2BI 355NHG2B 400NHG2B 425NHG2B 450NHG2B 500NHG2B 355NHG2BI 400NHG2BI 425NHG2BI** 450NHG2BI** 500NHG2BI** I2t (Amps2 Seconds) Fuse link size 2 Rated current (Amps) 250
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Time in seconds (s) Time-current curves - NH Size 03 Current in Amps (A) Technical data - NH size 03 Part numbers with metal gripping lugs 250NHG03B 315NHG03B 355NHG03B Part numbers with insulated metal gripping lugs 250NHG03BI 315NHG03BI 355NHG03BI 400NHG03B 400NHG03BI I2t (Amps2 Seconds) Fuse link size 03 Rated current (Amp) 250 315 355 400 Rated voltage (V a.c.
Bussmann series 500 Volts gG/gL NH Fuse links Technical Data 10164 Effective September 2015 Time in seconds (s) Time-current curves - NH Size 3 Current in Amps (A) Technical data - NH size 3 I2t (Amps2 Seconds) Part numbers with metal gripping lugs 315NHG3B 355NHG3B 400NHG3B 425NHG3B 450NHG3B 500NHG3B 630NHG3B 800NHG3B Fuse link size 3 Rated current (Amp) 315 355 400 Rated voltage (V a.c.) 500 500 500 Minimum pre-arcing 375,000 400,000 642,900 *I1 120kA at 500 V a.c.
Technical Data 10164 Bussmann series 500 Volts gG/gL NH Fuse links Effective September 2015 Time in seconds (s) Time-current curves - NH Size 4 Current in Amps (A) Technical data - NH size 4 I2t (Amps2 Seconds) Part numbers with metal gripping lugs 500NHG4G 630NHG4G 800NHG4G 1000NHG4G 1250NHG4G Fuse link size 4 Rated current (Amps) 500 630 800 1000 1250 Rated voltage (V a.c.) 500 Minimum pre-arcing 800,000 880,000 1,500,000 *I1 120kA at 500 V a.c.