Data Sheet

Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen.
Angegebene Werte nach NEC Table 430-150
230 V
240 V
HP Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen.
Angegebene Werte nach NEC Table 430-150
460 V
480 V
HP Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen.
Angegebene Werte nach NEC Table 430-150
575 V
600 V
HP Hinweis: Motorleistung in diesem Bereich nach Bemessungsstrom berechnen.
Angegebene Werte nach NEC Table 430-150
Short Circuit Current Rating, type E SCCR
240 V kA 65
480Y / 277V kA 65
600Y / 347V kA 50
Accessories required BK25/3-PKZ0-E
Short Circuit Current Rating, group protection SCCR
600 V High Fault
SCCR (fuse) kA 50
max. Fuse A 600
SCCR (CB) kA 50
max. CB A 600
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 0.63
Heat dissipation per pole, current-dependent P
vid
W 1.72
Equipment heat dissipation, current-dependent P
vid
W 5.16
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.