Data Sheet

DATASHEET - ZB12-2,4
Overload relay, ZB12, Ir= 1.6 - 2.4 A, 1 N/O, 1 N/C, Direct mounting, IP20
Part no. ZB12-2,4
Catalog No. 278437
Alternate Catalog
No.
XTOB2P4BC1
EL-Nummer
(Norway)
0004131832
Similar to illustration
Delivery program
Product range Overload relay ZB up to 150 A
Product range Accessories
Accessories Overload relays
Frame size ZB12
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
I
r
A 1.6 - 2.4
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILM7, DILM9, DILM12, DILM15,
DIULM7, DIULM9, DIULM12,
SDAINLM12,
SDAINLM16,
SDAINLM22
Short-circuit protection
Type “1” coordination gG/gL A 25
Type “2” coordination gG/gL A 10
Notes
Overload release: tripping class 10 A
short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors.
II(2)G [Ex d] [Ex e] [Ex px], II(2)D [Ex p] [Ex t]
PTB 10 ATEX 3010
Observe manual MN03407005Z-DE/EN.
Notes
Fitted directly to the contactor
06/18/2021 Eaton 278437 ED2021 V80.0 EN 1 / 6

Summary of content (6 pages)