Datasheet

03/13/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 5
Rated operational current I
e
A
AC-15
220/240 V I
e
A 4
60 Hz I
e
A 2
500 V I
e
A 1.5
DC L/R 15 ms
Contacts in series: A
1 24 V A 2.5
2 60 V A 2.5
3 100 V A 1.5
3 220 V A 0.5
Conv. thermal current I
th
A 10
Control circuit reliability (at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA) Failure
rate
λ
<10
-8
, < one failure at 100 million operations
Component lifespan at U
e
= 240 V
AC-15 Operations x
10
6
0.2
DC
Footnote Switch-on and switch-off conditions based on DC-13, time constant as
specified
L/R = 50 ms: 2 contacts in series at I
e
= 0.5 A Operations x
10
6
0.15
Short-circuit rating without welding
Maximum overcurrent protective device
Short-circuit protection only PKZM0-4
Short-circuit protection maximum fuse
500 V A
gG/
gL
6
500 V A
fast
10
Current heat loss at I
th
Per contact W 0.2
Technical�data�according�to�ETIM�4.0
Suitable for earth leakage circuit breaker No
Type of electric connection Screw connection
Rated operation current Ie at AC-15, 230 V A 4
Mounting type Front mount
Suitable for pendant switch No
Suitable for front element No
Suitable for circuit-breakers No
Suitable for safety position switches No
Suitable for step switches No
Suitable for pressure switch/selector switch actuator No
Suitable for cam switches No
Suitable for motor protective circuit breakers No
Suitable for series-mounting relays No
Suitable for solenoid No
Suitable for compact switch-disconnector No
Suitable for miniature circuit-breakers No
Suitable for pulse relay No
Suitable for contactor relay relay YES
Suitable for pendant pushbutton No
Suitable for residual current device No
Number of contacts as change-over contact 0
Number of contacts as N/O 4