Datasheet

5
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 000
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
Technical data - NH size 000
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
2NHG000B 2NHG000BI 000 2 500 3.5 6 3.9 0.13
4NHG000B 4NHG000BI 4 6 12 1.8
6NHG000B 6NHG000BI 6 14 21 2
10NHG000B 10NHG000BI 10 58 290 1.5
16NHG000B 16NHG000BI 16 234 1200 2.3
20NHG000B 20NHG000BI 20 490 2500 2.2
25NHG000B 25NHG000BI 25 920 4600 3.1
32NHG000B 32NHG000BI 32 1800 9000 3.4
35NHG000B 35NHG000BI 35 2400 11,800 3.7
40NHG000B 40NHG000BI 40 3300 16,500 4
50NHG000B 50NHG000BI 50 5900 29,500 4.9
63NHG000B 63NHG000BI 63 6300 24,900 4.6
80NHG000B 80NHG000BI 80 9800 38,900 6.3
100NHG000B 100NHG000BI 100 18,100 72,300 7.4
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements