Datasheet

6
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 00
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
Technical data - NH size 00
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
50NHG00B 50NHG00BI** 00 50 500 5800 21,500 5 0.19
63NHG00B 63NHG00BI** 63 5800 25,000 5
80NHG00B 80NHG00BI** 80 11,000 35,000 7
100NHG00B 100NHG00BI** 100 19,000 60,000 7.5
125NHG00B 125NHG00BI 125 25,000 125,000 10
160NHG00B 160NHG00BI 160 64,000 310,000 10
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
** Available upon request