7
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 0
TIME (Seconds)
CURRENT (Amperes)
684268 2 648 246
10 100 1000
2
6
4
0.1
0.01
1
6
4
2
6
2
4
10
100
6
4
2
6
4
2
6
4
2
1 000
10 000
32
35
40
50
63
80
100
125
160
16
10
20
25
6
Technical data - NH size 0
Part numbers
with metal
gripping lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
6NHG0B 0 6 500 14 21 2 0.26
10NHG0B 10 58 290 2
16NHG0B 16 240 1200 3
20NHG0B 20 490 2500 3.5
25NHG0B 25 1200 5600 3.2
32NHG0B 32 1800 9000 4.8
35NHG0B 35 2400 11,800 4.7
40NHG0B 40 3300 16,500 5
50NHG0B 50 5600 27,800 6.3
63NHG0B 63 6600 26,100 5.6
80NHG0B 80 9800 38,900 7.1
100NHG0B 100 20,600 82,300 7.5
125NHG0B 125 25,000 125,000 11.8
160NHG0B 160 62,000 310,000 12.3
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
Time in seconds (s)