User`s guide

Specifications
36
Powerware
®
5115 Tower UPS (500–1400 VA) User’s Guide S 05146640 Rev C www.powerware.com
Table 5. Electrical Output
120V Models 230V Models
Power Levels (rated at
nominal inputs)
500 VA, 320W
750 VA, 500W
1000 VA, 670W
1400 VA, 950W
Power Factor
500 VA, 0.64
750–1400 VA, 0.67
Regulation (Normal
mode)
-10% to +6% of nominal voltage
Regulation (Battery
mode), Nominal
Voltage ±5%
Same as selected nominal input
voltage
110V, 120V
Same as selected nominal input
voltage
220V, 230V, 240V
Voltage Waveform
Sine wave
Overcurrent Protection
Inverter saturation current limited
Output Receptacles
500–750 VA: (4) 5-15
1000–1400 VA: (6) 5-15
500–750 VA: (4) 10A, I EC-320
1000–1400 VA: (6) 10A, I EC-320
Table 6. Environmental and Safety
120V Models 230V Models
Operating
Temperature
Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 55°C (5°F to 131°F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,000 meters above sea level
Audible Noise
Less than 45 dBA typical
Surge Suppression
ANSI C62.41 Category A (formerly IEEE 587)
Safety Conformance
UL 1778; UL 497A;
CSA C22.2, No. 107.1
UL 1778, UL 497A (data line only);
CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
Safety Markings
UL, cUL UL, cUL, CE, TÜV, C-Tick
EMC(ClassB)
FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003