User`s guide

Specifications
37
Powerware
®
5115 Tower UPS (500–1400 VA) User’s Guide S 05146640 Rev C www.powerware.com
Table 7. Battery
Configuration
500 VA: (1) 12V, 9 Ah internal battery
750 VA: (2) 12V, 7 or 7.2 Ah internal batteries
1000 VA: (2) 12V, 9 Ah internal batteries
1400 VA: (3) 12V, 9 Ah internal batteries
Voltage
500 VA: 12 Vdc
750–1000 VA: 24 Vdc
1400 VA: 36 Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Advanced charging for faster recovery; approximately 3 hours to 90% usable
capacity at nominal line and no supplementary power supply load
Monitoring
Advanced monitoring for earlier failure detection and warning
Table8.BatteryRunTimes(inMinutes)
UPS Models by VA Ratings
Load (VA) Watts 500 750 1000 1400
200 128 17 38 41 58
300 192 11 27 28 41
500 320 5 14 15 28
600 402 9 10 19
750 503 6 8 14
900 603 6 10
1000 670 5 8
1200 804 6
1400 938 5
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.