User Manual

Page 13
614-07977-00_EN
ENGLISH
3. Installation
3.4 Communication ports
Connection of RS232 or USB communication port (optional)
The RS232 and USB communication ports cannot operate simultaneously.
1. Connect the RS232 (33) or
USB (34) communication cable
to the serial or USB port on
the computer equipment.
2. Connect the other end of the
communication cable (33) or
(34) to the USB (1) or RS232
(2) communication port on
the UPS.
The UPS can now communicate
with EATON power management
software.
Installation of the communication cards (optional, standard on the Netpack versions)
It is not necessary to shutdown
the UPS before installing
a communication card.
1. Remove the slot cover (4)
secured by screws.
2. Insert the communication
card in the slot.
3. Secure the card cover with
the 2 screws.
Characteristics of the contact communication port (optional)
Pins 1, 3, 4, 5, 6, 10: not used p
Pin 2: common (user) p
Pin 7: low battery p
Pin 8: operation on battery p
power
Pin 9: UPS ON, equipment p
supplied
n.o.: normally open contact
When a signal is activated, the contact is closed between the common (pin 2) and the pin
for the corresponding signal.
Contact characteristics (optocoupler)
Voltage: 48 V DC max p
Current: 25 mA max p
Power: 1.2 W p