Powerware series Eaton 9155 UPS 8-15 kVA
Product Introduction Product Snapshot Technology: Split-phase double-conversion online UPS Power Rating: 8 kVA, 10 kVA, 12 kVA and 15 kVA at 0.9 power factor Input Voltage: 200–240 Vac with Neutral or with optional input isolation transformer Output Voltage: 100/200, 110/220, 120/240 Vac 180° phase displacement; 120/208, 127/220 Vac 120° phase displacement Frequency: 50/60 Hz auto-sensing Dimensions: 32.2” H x 12” W x 32.
Premium power protection is now easier than ever. Scalable architecture meets current and future load requirements. With raised-floor real estate at a premium, you’ll appreciate that the 9155 requires only three to six square feet of floor space, including internal batteries. Such a small footprint gives you more location options and more space available for future expansion.
Options & service Additional 9155 options Wall-mount maintenance bypass panels Eaton offers a comprehensive line of optional wall-mounted maintenance bypass panels compatible with the 9155 UPS. The wall-mounted bypass panel is used to bypass the UPS during maintenance or servicing, providing wrap-around bypass for UPS service without shutting down the load.
Connectivity & manageability Enhanced communication capabilities Power Xpert® Gateway Series cards Power Xpert Gateway Series X-Slot cards provide Web-enabled, real-time monitoring of UPSs, PDUs and RPPs through standard onboard Web pages, Power Xpert software or third-party software.
Eaton 9155 at-a-glance Model Selection Table - Eaton 9155 UPS (8–15 kVA) Power Rating2 (kVA/kW) Order Number1 Description Input & Output Dimensions Connection4 Output Receptacles H x W x D5 (in) Unit Weight3 (lb) K4081100000 PW9155 Model 8 - 32 Battery (2-high) 8/7.2 Hardwired See PDM chart 32.2 x 12.0 x 32.0 352 K4081200000 PW9155 Model 8 - 64 Battery (3-high) 8/7.2 Hardwired See PDM chart 47.8 x 12.0 x 32.0 590 K4081300000 PW9155 Model 8 - 32 Battery with Transformer (3-high) 8/7.
Eaton 9155 Accessories Accessories Description Dimensions H x W x D (in) Unit Weight (lb) 124100017-001 9155 Parallel Cabinet 24.0 x 20.3 x 2.2 57.3 103004336 Powerware HotSync CAN Bridge Card - - Order Number Powerware Hot Sync Notes: Up to three 9155 UPS and up to four 9355 UPS (available Fall 2005) UPSs can be paralleled with the Parallel Cabinet. Extended Battery Module (EBM) or Cabinets (EBC) 103004192-5501 9155 and 9355 EBM 64 (2-high) 32.2 x 12.0 x 30.
TECHNICAL SPECIFICATIONS for 10 AND 15 kVA Environmental Power Ratings (kVA/Watts) 8, 10, 12 and 15 kVA at 0.9 power factor Topology True double-conversion online UPS Electrical Input Nominal Input Voltage 200V-240V with neutral or with optional input transformer Input Voltage Range -15%, +10% from nominal at 100% load without depleting battery Operating Temperature 10ºC to +40ºC, +45ºC with 7.5% derating; Batteries recommended max.