Installation guide

1027574 UPS 450-550 kVA (2x225 - 2x275 kVA) 79
Revision E User’s and Installation Guide
Service History The Service History Log is for service personnel and is password protected.
If the customer needs access to the log, contact an Eaton service represen-
tative. Press the SERVICE pushbutton on the User History menu bar to dis-
play the Service History Log. The Service History Log lists up to 2048
events in chronological order, with the most recent event listed last (once
2048 is reached, the earliest event is overwritten). The end of the log (the
most recent events) is displayed first; scroll upward to view older event
listings. To scroll through the events, press the up or down arrow pushbut-
ton on the menu bar. To return to the User History screen, press the USER
pushbutton on the menu bar. To return to the Active Events screen, press
the EVENTS pushbutton on the menu bar.
Meters - UPS
Meters - UPM
The Meter screens show the UPS meter readings for the unit. The default
voltage displayed on these screens is phase-to-neutral. However, an autho-
rized Eaton Customer Service Engineer can change the screens to display
the voltage phase-to-phase (L1-L2, L2-L3, L3-L1). Press the METERS push-
button on the main menu bar to display the Meter screens. To scroll
through the meter screens, press the up or down arrow pushbutton on the
menu bar. The current UPS readings are displayed in the information area
of the screen.
Output - UPS
Output - UPM
The Output screen shows output voltage (phase-to-neutral), output current
(each phase), and frequency being supplied by the UPS, as well as the kVA,
kW, and power factor measurements.
Input - UPS
Input - UPM
The Input screen shows input voltage (phase-to-neutral), input current
(each phase), and frequency of the incoming utility source, as well as the
kVA, kW, and power factor measurements.
Bypass The Bypass screen shows the bypass input voltage (phase-to-neutral),
input current (each phase), and frequency of the incoming utility source, as
well as the kVA, kW, and power factor measurements.
Battery - UPS
Battery - UPM
The Battery screen displays the battery voltage (Vdc), the battery current
(Idc), the minutes of battery time remaining, and battery temperature. Bat-
tery temperature must be set up by an authorized Eaton Customer Service
Engineer. When battery life decreases to less than 20%, Check Battery is
displayed.
Statistics The Statistics screen displays the hours on line and the total kW hours
used.
Output Current - UPS
Output Current -UPM
The Output Current screen displays a real-time bar graph of the output cur-
rent of the UPS. The graph shows the current for each phase.
Output Power - UPM The Output Power screen displays the power in kW and kVA for each UPM.
System Level 0
Setup
Function Selection This screen can be used to set the screen contrast, show the firmware ver-
sions installed, identify the unit type, change the display language, set up
Energy Saver functions, set up Advanced Power Management functions,
and enter a password to access Level 1 functions.
Press the SETUP pushbutton on the main menu bar to display the System
Setup Level 0 Screen. No password is necessary to access Level 0 func-
tions. Use the up or down arrow pushbutton to highlight the setup function
screen desired, then press the SELECT pushbutton to display the function
screen.
Function Subfunction Operation