Operating instructions

Eaton 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual S 164201716 Rev 2 www.eaton.com/powerquality
10-1
Chapter 10 Product Specifications
10.1 Model Numbers
The UPS is housed in a free‐standing cabinet with safety shields behind the door and
front panels. The UPS is available in 50 or 60 Hz with various output power ratings.
Models Power Rating Frequency
Eaton 9395-550/225 225 kVA 50/60 Hz
Eaton 9395-550/275 275 kVA 50/60 Hz
Eaton 9395-550/450 450 kVA 50/60 Hz
Eaton 9395-550/500 500 kVA 50/60 Hz
Eaton 9395-550/550 550 kVA 50/60 Hz
10.2 Specifications
The following sections detail the input, output, battery, and environmental
specifications for the UPS.
10.2.1 UPS Input
Operating Input Voltage 400 Vac
480 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 3‐4 through Table 3‐8 starting on page 3-9.
Reduced for Generator
Adjustable
Input Current Harmonic Content 5% THD at full load
Power Factor Minimum 0.99
Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
Battery Voltage 480 Vdc
Battery Charging Capacity Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip 48 Vdc