Eaton 93PM UPS 30-200 kW User's and Installation Guide P-164000249
Eaton 93PM UPS 30-200 kW User's and Installation Guide
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. This is a product for commercial and industrial application in the second environment. Installation restrictions or additional measures may be needed to prevent disturbances.
Contents 1 Safety instructions......................................................................................................................................................................................................................... 1 1.1 Audience...................................................................................................................................................................................... 3 1.2 CE marking...................................................
.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.1.1 Control panel................................................................................................................................................................. 58 6.1.2 Status indicators............................................................................................................................................................ 60 6.1.3 System events...........................................................................................
List of Figures Figure 1-1: Recycling batteries symbol................................................................................................................................................. 5 Figure 1-2: WEEE symbol......................................................................................................................................................................6 Figure 2-1: Eaton 93PM UPS.............................................................................................
List of Tables Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table iv 2-1: UPS configurations..............................................................................................................................................................23 2-2: Standard and optional UPS options.................................................................................................................................... 23 3-1: Dimensions.....
1 Safety instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. The UPS operates with mains, battery or bypass power. It contains components that carry high currents and voltages.
WARNING 2 • The UPS is powered by its own energy source (batteries). The output terminals may be energised even when the UPS is disconnected from an AC source. To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40 °C (104 °F). Do not operate near water or excessive humidity (95 % maximum). The system is not intended for outdoor use.
CAUTION • Installation or servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. Consider all warnings, cautions, and notes before installing or replacing batteries. DO NOT DISCONNECT the batteries while the UPS is in Battery mode. • Replace batteries with the same number and type of batteries as originally installed in the UPS.
• EMC Directive 2004/108/EC Declaration of conformity with UPS harmonised standards and directives EN 62040-1 (Safety) and EN 62040-2 (EMC) are available at www.eaton.eu/93PM or by contacting your nearest Eaton office or authorized partner. 1.3 User precautions The only user operations permitted are: • Start up and shut down of the UPS, excluding the commissioning start up. • Use of the LCD control panel and Maintenance Bypass Switch (MBS). • Use of optional connectivity modules and their software.
WARNING Hydrogen and oxygen gases are emitted from batteries into the surrounding atmosphere during charge, float charge, heavy discharge, and overcharge. Explosive gas mixture may be created if the hydrogen concentration exceeds 4 % by volume in air. Necessary air flow rate for ventilation of UPS location must be ensured. As an example, for 93PM 30-50 kW UPS, a minimum air flow is 5 m³/ hour for the room where one 93PM UPS with internal VRLA batteries is placed.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Figure 1-2: WEEE symbol 1.6 Conventions used in this manual This manual uses these type conventions: • Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or represents a command or option that you type or enter at a prompt.
• Regional locations and telephone numbers • A question about any of the information in this manual • A question this manual does not answer P-164000249 Revision 2 30-200 kW User's and Installation Guide 7
2 Introduction to Eaton UPS The Eaton® 93PM uninterruptible power supply (UPS) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, supplying conditioned and uninterruptible AC power to critical load and protecting it from power failures. The UPS is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
Figure 2-1: Eaton 93PM UPS 2.1 Looking inside the UPS system The system level static bypass in the Eaton 93PM UPS cabinet determines the attainable output power of the UPS. The static bypass line consists of static switch and a backfeed protection isolation device connected in series. In addition, there is a system level control unit that constantly monitors the power delivered through the bypass line or to the input of the UPS.
The 30-50 kW 93PM UPS includes a 50 kW rated static bypass section, one UPM power module, and internal batteries. In addition to the internal batteries, also external batteries can be connected. The main components of this UPS are depicted in Figure 2-2: 93PM 50 kW UPS wiring diagram on page 11.
Figure 2-2: 93PM 50 kW UPS wiring diagram P-164000249 Revision 2 30-200 kW User's and Installation Guide 11
In the 80-200 kW units, the UPM power modules are paralleled internally. These units do not include internal batteries. Figure 2-3: 93PM 150 kW UPS wiring diagram on page 12 shows the construction of the 150 kW 93PM UPS with three power modules.
The rectifier input switch and battery breaker are available as standard for the 30-50 kW units, and as optional for the 80-150 kW units. The internal MBS is available as optional for the 30-150 kW units. These options are not available for the 160-200 kW units, and will have to be included externally in the installation.
Internal relay contacts Figure 2-4: Path of current through the UPS in double conversion mode Three-phase AC input power is converted to DC using a multilevel converter with IGBT devices to produce a regulated DC voltage to the inverter. The UPS status indicated on the display is “Unit Online” and the UPM status is “Active”. The battery converter derives its input from the regulated DC output of the rectifier and provides regulated charge current to the battery.
2.2.1.2 Energy Saver System mode In ESS mode the UPS safely provides mains current directly to the load when the input is within the acceptable limits by its voltage and frequency. The UPS status indicated on the display is “Unit Online ESS”, and the UPM status is “Active”. Surge protection and some filtering is also provided, ensuring that clean power is delivered to the load equipment.
Internal relay contacts Battery breaker Figure 2-6: Path of current through the UPS in battery mode During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output current required to support the inverter. The input relay K1 opens and the UPS output is powered from batteries through the inverter. As the inverter operates uninterrupted through the transition, the load remains supported continuously without disturbance.
NOTE The critical load is not protected while the UPS is in Bypass mode. Internal relay contacts Figure 2-7: Path of current through the UPS in bypass mode In bypass mode, the output of the system is provided with three-phase AC power directly from the system input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or power outages from the source.
2.3.1 Advanced Battery Management Advanced Battery Management technology uses sophisticated sensing circuitry and a three-stage charging technique that extends the useful service life of UPS batteries while optimizing the battery recharge time. ABM also protects batteries from damage caused by high current charging and inverter ripple currents. Charging at high currents can overheat and damage batteries. In charge mode, the batteries are recharged.
2.5 Options and accessories Contact an Eaton sales representative for information about the available options. 2.5.1 Maintenance Bypass Switch The Maintenance Bypass Switch (MBS) enables power to completely bypass and isolate the UPS so that the UPS can be safely serviced or replaced without interrupting power to critical systems. An internal maintenance bypass switch is provided as a factory installed option for 30-150 kW units.
1. Maintenance Bypass Switch (MBP) 2.
1. Bypass Input Breaker (BIB) 2. Maintenance Isolation Switch (MIS) 3. Maintenance Bypass Switch (MBP) Figure 2-9: Three-switch MBS electrical connection drawing For external MBS installation instructions, see a separate manual.
2.5.2 Top air exhaust kit The top air exhaust kit is used to direct the UPS cooling air front-to-top. The kit will eliminate the cooling clearance requirement from the back of the unit, and enable installing the 93PM UPS even against a wall, in a corner or back-to-back. The kit increases the depth of the unit by 200 mm. Refer to Chapter 3.2 Site preparations on page 25 for further information. 2.5.
2.7 Basic system configurations UPS power rating The maximum attainable UPS system power rating is determined by the size of static bypass. The number of UPM power modules determines the nominal power rating of the UPS. If upgradeability is required, the system static bypass should be chosen according to the future maximum load rating, and number of UPMs is chosen according to Day1 capacity requirements.
30-50 kW 80-100 kW 120-150 kW 160-200 kW Rectifier input switch IS Standard Option Option - Internal battery breaker BB Standard Option Option - - Option Option Option Battery start Standard Standard Standard Standard Integrated backfeed protection Standard Standard Standard Standard Chimney / front-to-top air flow Table 2-2: Standard and optional UPS options Additional options and accessories are also available.
3 UPS installation plan and unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system 2. Prepare your site for the UPS system 3. Inspect and unpack the UPS cabinet 4. Unload and install the UPS cabinet, and wire the system 5. Complete the installation checklist (Chapter 10 Installation checklist on page 82) 6. Have authorized service personnel perform preliminary operational checks and startup.
Failure to follow guidelines may void your warranty.
30-50 kW 80-200 kW From top of cabinet 500 mm 800 mm From front of cabinet 900 mm 900 mm From back of cabinet 0 mm 0 mm Table 3-4: UPS cabinet minimum clearances with top air exhaust kit • X = clearance at back of cabinet • Y = clearance at top of cabinet Figure 3-1: UPS cabinet clearances. See Table 3-3.
Rating Heat rejection (BTU/h x 1000) Heat rejection (kW) 30 kW 4.30 1.3 40 kW 5.73 1.7 50 kW 7.16 2.1 80 kW 11.45 3.4 100 kW 14.32 4.2 120 kW 17.18 5.0 150 kW 21.48 6.3 160 kW 22.91 6.7 200 kW 28.64 8.
Figure 3-3: 93PM 160-200 kW UPS dimensions Figure 3-4: Eaton 93PM 80-150 kW UPS Top air exhaust kit dimensions P-164000249 Revision 2 30-200 kW User's and Installation Guide 29
Figure 3-5: Eaton 93PM 200 kW UPS Top air exhaust kit dimensions 3.2.2 UPS system power wiring preparation NOTE If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a single feed with two upstream feeder breakers, must be provided: one for the UPS or rectifier input breaker (if installed) and one for the maintenance bypass input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or rectifier input breaker and the maintenance bypass.
• The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses three or four wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment operation. • If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor connected at the bypass input, a neutral must be installed to source star point.
Rated power 80 kW 100 kW 120 kW 150 kW 160 kW 200 kW Battery Battery Rated current Max.
Terminal function Terminal Function Tightening torque Nm AC input to UPS rectifier X1 L1, L2, L3, N Check the tightening torque from the connector label. AC input to bypass X2 L1, L2, L3, N Check the tightening torque from the connector label. UPS output X3 L1, L2, L3, N Check the tightening torque from the connector label. DC input from external battery to UPS X4 battery +, battery – Check the tightening torque from the connector label.
3.2.3 UPS system interface wiring preparation Control wiring for features and options should be connected at the customer interface terminal blocks located on top front of the UPS, behind the door. DANGER Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: • All interface wiring is to be provided by the customer.
NOTE The UPS cabinet is heavy. If unpacking instructions are not closely followed, the cabinet may tip and cause serious injury. The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform the following procedure: 1. If not already accomplished, use a forklift or other material handling equipment to move the cabinet to the installation area, or as close as possible, before unloading from the pallet.
4 UPS system installation The customer has to supply the wiring to connect the UPS to the local power source. The electrical installation procedure is described in the following section. The installation inspection and the initial start-up of the UPS and installing an extra battery cabinet must be carried out by qualified service personnel such as a licensed service engineer from the manufacturer or from an agent authorized by the manufacturer.
13. When all wiring is complete, reinstall safety shield panels removed in previous steps. 14. Close the door and secure with latch. 15. If installing a parallel system, repeat the above steps to all units in the system.
Figure 4-2: 93PM 80-150 kW UPS gland plate and connector locations 38 30-200 kW User's and Installation Guide P-164000249 Revision 2
Figure 4-3: 93PM 160-200 kW UPS gland plate and connector locations Top cable access kit The following figure shows the top cable access kit for 30-150 kW UPS units. The top cable access kit is optional. For more information, see Chapter 2.5.3 Top cable access kit on page 22.
Figure 4-4: 93PM 30-150 kW Top cable access kit 4.2 Battery system installation This UPS may have internal batteries. Connection of these batteries is to be left to the responsibility of the commissioning personnel in order to avoid damages to the equipment or personal injuries in case of an incorrect connection. The batteries are designed to deliver a large amount of energy and an incorrect connection may lead to short circuit and cause serious injuries to the personnel or damages to the equipment.
4.3 Installing UPS external battery cabinet and battery power wiring For the 93PM product line, there are two different battery cabinets: EBC-S and EBC-L. The 93PM 30-50 kW UPS uses 36 battery blocks per string, and the 80-200 kW UPS uses 36 or 40 battery blocks per string. NOTE Battery strings with different battery quantity and voltage may not be connected in parallel. Power and control wiring for integral line-up and match battery cabinets are supplied with the cabinets.
Figure 4-5: 93PM battery cabinet (EBC-S) 42 30-200 kW User's and Installation Guide P-164000249 Revision 2
Figure 4-6: 93PM battery cabinet (EBC-L) P-164000249 Revision 2 30-200 kW User's and Installation Guide 43
Figure 4-7: UPS cabinet through holes A DC-rated circuit breaker within each cabinet provides protection and servicing isolation. The battery cabinets use convection cooling to regulate internal component temperature. Air inlets are on the bottom, and in EBC-L also in the front of the cabinet and outlets are in the top back of the cabinet. Clearance must be allowed in front and back of each cabinet for proper air circulation.
8. If multiple cabinets are to be used, repeat the steps to the rest of the cabinets and be sure to daisy chain the signal wire harnesses in the next cabinet. NOTE The battery cabinet is heavy. If unpacking instructions are not closely followed, the cabinet may tip and cause serious injury. Preparing the EBC-L cabinet installation 1.
Figure 4-8: Connections of the EPO switch From remote EPO switch To customer interface Terminal block EPO in UPS cabinet NO 1-2 NC 3-4 Remarks Wire jumper between 1-2 must be installed for proper functions. Table 4-1: Remote EPO wire terminations 4.5 Installing interface connections 93PM UPS contains a total of five (5) signal input connectors for customers which can be used for giving remote control commands to the UPS. Customer interface connector CN5 can be used for these purposes.
4.5.2 Battery breaker wiring interface When using the original accessory battery cabinet from the manufacturer, the battery breaker interface wiring is provided with the cabinet. Connecting it requires only routing the wires from the cabinet to the bottom section of the UPS. The connector for the battery circuit breaker monitoring signal and battery circuit breaker trip signal are to the left from the power cabling.
4.6 Wiring parallel 93PM UPS systems The outputs of multiple 93PM UPS systems can be connected in parallel. Up to four (4) units can be paralleled. The UPS static bypass power rating needs to be identical among all paralleled units. However, paralleled UPS cabinets can be housed with different number of UPM power modules. The outputs are paralleled to increase the load capacity of the power system and for redundancy.
MOB’s Module Output Breakers (MOBs) allow the output of the UPS to be disconnected from the other UPSs and system load for maintenance and service. Design considerations assume that each UPS has a Module Output Breaker (MOB). The breaker shall not disconnect neutral. The MOB must have a Form “C” auxiliary contact. The N.C contact is connected to the corresponding UPS’s input used for signal input. The N.O. contact is used to disconnect the Bypass Pull-Chain when the MOB is open.
4.6.2 Control signals overview Two controls signals (External CAN Network, Bypass Pull-Chain) are required for external paralleling. Both of these control signals are fault tolerant and alarmed when disconnected. External CAN (ECAN) ECAN provides means for communications between the UPS’s in a parallel system. The system will continue to share load and protect the load when this network fails.
Figure 4-11: Simplified CAN and Pull-Chain wiring for parallel UPS system NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order. NOTE External CAN connections between UPSs require shielded twisted pair wire. NOTE Use twisted pair wiring between the UPS and MOB AUX contacts.
Figure 4-13: CAN and Pull-Chain wiring for parallel UPS without MOBs NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position. If MOB contacts have pigtail leads, use the same wire gauge to connect to the UPS and use the correct crimp connections for the wire gauge. External CAN connections between UPS cabinets require shielded twisted pair wire. Use twisted pair wiring between the UPS and MOB AUX contacts. Always confirm contact operation prior to wiring.
5 Communication interfaces This section describes the communication features of the Eaton 93PM UPS. The UPS has the following communication interfaces: 1. Mini-slot 1 2. Mini-slot 2 3. Mini-slot 3 4. USB device (connection to computer) 5. Communication cable conduit 6. Emergency Power Off (EPO) 7. Relay output 8. USB host (connection to accessories) 9. Signal inputs 10. RS-232 port for service 11. External parallel connector Figure 5-1: Communication interfaces 5.
Figure 5-2: Network Card-MS • PX Gateway Card Provides remote monitoring through a Web browser interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT) network. The card also provides direct integration of UPS information (meters and status) to a Building Management System (BMS) using the Modbus RTU and TCP protocols. Figure 5-3: PX Gateway Card • Relay Card-MS Two types of interfaces via a DB9 connector are available with this card.
Figure 5-4: Relay Card-MS • Network and MODBUS Card - MS Provides remote monitoring through a Web browser interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT) network. The card also provides direct integration of UPS information (meters and status) to a Building Management System (BMS) using the Modbus RTU protocol.
Figure 5-6: Industrial Relay Card-MS 5.2 Intelligent Power Software Intelligent Power Software are productivity tools for UPS power management. The Intelligent Power Protector (IPP) application provides automatic, graceful shutdown of computers and virtual machines or servers powered by an Eaton UPS during a power outage that lasts longer than your available battery runtime. Intelligent Power Protector can be remotely supervised and managed by the Intelligent Power Manager (IPM) application.
NOTE Contacts should not be operated in excess of 30 VAC (RMS) and 30 VDC at 5 A maximum.
6 UPS operating instructions This section describes how to operate the UPS. NOTE Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the system operates properly. Read these instructions and have a thorough understanding of UPS operation before attempting to operate any of the controls.
Figure 6-1: Parts of the display The display consists of the following parts: • A: Status bar The status bar displays the UPS name, state, current date and time, meters information, and a sign in/out button. Active alarms and warnings are also shown. • B: Main navigation Select a screen by tapping on its name. • C: Secondary navigation/additional information bar The bar displays buttons and selectors related to the current screen.
6.1.2 Status indicators The four symbols below the display are status indicators. They are colored light emitting diode (LED) lamps, and they work in conjunction with the alarm horn to let you know the operating status of the UPS. Indicator Status Description Green On The UPS is operating normally and supplying power to the critical load. Off The UPS is turned off. On The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the Normal indicator also remains illuminated.
6.1.3 System events When the UPS system is running in Double conversion mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Double conversion mode. System events on the UPS can be indicated by horns, lights, messages, or all three. Select Logs from the main menu screen to look at any currently active events.
Main menu Logs Statistics Controls Settings Submenu Functions UPS module map Module map shows the status of each UPM. System overview System overview shows the status and meters summary for each UPS. ESS ESS mimic screen shows the approximated consumption and energy savings of ESS mode. Active events All active events are displayed. System log A log of all system events. Service log A detailed log of UPS operations. Change log A log of all changed settings and their values.
1. 2. 3. button in the upper right corner of the screen. Press the lock Type your passcode and press OK. You are signed in. Press Continue to return to the previous screen. There are three attempts to input the password. If an incorrect password is given more than three times, you need to wait for 30 minutes before trying again. To modify the user settings, you need to enter level 2 password. For the default passwords, see Chapter 11 APPENDIX A: User settings on page 84. 6.
6.4.2 Starting the UPS system in Bypass mode If the inverter output of the UPS is not available and the critical load needs to be energized, perform the following procedure: CAUTION In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities. 1. 2. 3. 4. 5. 6. 7. 8. 9. Unfasten the front door latch and swing the door open.
6.4.4 Transfer from Bypass to Double conversion mode To transfer the critical load to double conversion mode, perform the following procedure: 1. 2. 3. Press the Controls button in the main menu. The System controls screen appears. Press the Go online button on the System controls screen. The UPS system transfers to double conversion mode. If enough UPM capacity is not available, the system remains on bypass and an alarm sounds.
6.4.7 UPS system and critical load shutdown To perform maintenance or service on the critical load, shut down power to the load by performing the following procedure: 1. 2. Turn off all equipment that is being powered by the UPS system. Perform the LOAD OFF procedure (see Chapter 6.4.8 De-energizing the Critical Load on page 66). The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the power module is turned off.
3. To restart the UPS system, follow the procedure in Chapter 6.4.1 Starting the UPS system in Double conversion mode on page 63 or Chapter 6.4.2 Starting the UPS system in Bypass mode on page 64. 6.5 UPS control instructions 6.5.1 Starting a single UPS Ensure that load level does not exceed single UPS capacity. To start the UPS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Unfasten the front door latch and swing the door open.
6.5.3 Enabling and disabling the battery charger To turn the battery charger on or off, perform the following procedure: 1. 2. 3. Press the Controls button in the main menu. The System controls screen appears. On the System controls screen, press UPS controls. Press the Start charger / Stop charger button. 6.6 UPM control instructions 6.6.1 Starting the UPMs Make sure that load level does not exceed single UPM capacity. To start an individual power module in double conversion mode: 1. 2. 3. 4. 5. 6. 7. 8.
4. On the UPM control screen, select Shut down module. 6.7 Using the Remote Emergency Power-off switch A UPS emergency power-off is initiated by the EPO pushbutton switch. In an emergency, you can use this switch to control the UPS output. The EPO switch de-energizes the critical load and powers down the UPS immediately, without asking for verification. The UPS, including Bypass, remains off until restarted.
NOTE The integral MBS and Static Bypass need to supplied by the same source. To turn the UPS to mechanical bypass switch: 1. The normal start position should be following: Maintenance Bypass Switch (MBS) Figure 6-6: The normal positions of the MBS switches and rectifier disconnect switch (must be located in the site wiring) 2. 3. 4. 5. 6. Perform transfer from double conversion mode to bypass mode as described in Chapter 6.4.3 Transfer from Double conversion mode to Bypass mode on page 64.
6.9 Turning UPS from mechanical bypass to double conversion mode To turn the UPS back to double conversion mode: 1. The normal start position should be the following: Figure 6-8: Mechanical bypass mode 2. 3. 4. 5. 6. Turn ON rectifier switch to connect rectifier input to UPS. Turn ON Static bypass switch to connect bypass input to UPS: Perform the UPS start-up procedure (bypass mode) in Chapter 6.4.2 Starting the UPS system in Bypass mode on page 64.
7 UPS maintenance The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly.
7.2 Performing preventive maintenance The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that the batteries are in good condition. Majority of the work must be performed by Eaton authorized service personnel. Only the actions described in Chapter 7.2.1 DAILY maintenance on page 73 and Chapter 7.2.2 MONTHLY maintenance on page 73 are allowed for the user. 7.2.
NOTE Work on energized circuit must be performed only by authorized personnel. 7.2.4 ANNUAL maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact your service representative for more information about service offerings. 7.2.5 BATTERY maintenance Contact your service representative for battery maintenance.
DANGER HAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES, and CAUSTIC, TOXIC and FLAMMABLE substances. Batteries can injure or kill people and damage equipment if used improperly. DO NOT DISCARD unwanted batteries or battery material in the public waste disposal system. Follow ALL applicable, local regulations for storage, handling and disposal of batteries and battery materials. Figure 7-2: Recycling batteries symbol 7.
8 Technical data For complete technical specification, contact your Eaton representative. Due to continuous product improvement programs, specifications are subject to change without notice. 8.1 Standards Safety: IEC 62040-1, IEC 60950-1 EMC, Emissions: IEC 62040-2/Ed.
8.
Total voltage harmonic distortion <1% 100 % linear load <5% 100 % non-linear load Rated output frequency 50 or 60 Hz, configurable Output frequency variation ± 0,1 Hz Slew rate 1 Hz/s Overload capability at ambient 40 °C (On inverter) 10 min 102-110 % load 60 sec 111-125 % load 10 sec 126-150 % load 300 ms > 150 % load Overload capability at ambient 40 °C (On inverter, stored energy mode) 10 min 102-110 % load 60 sec 111-125 % load 300 ms > 126 % load Overload capability at ambient 40 °C (On b
Battery quantity 30-50 kW units: 36 blocks, 216 cells per battery string 80-200 kW units: 36 blocks, 216 cells per battery string, or 40 blocks, 240 cells per battery string Note! Battery strings with different battery quantity and voltage may not be connected in parallel! Battery voltage 432 V (36 blocks) or 480 V (40 blocks) Recharge profile ABM or float charge End of discharge voltage 1.67 VPC to 1.
Ambient service temperature range, (UPS) From +5 °C to +40 °C* No output power derating required. Relative humidity range 5 to 95 %, no condensation allowed Maximum service altitude 1000 m (3300 ft) above sea level Maximum 2000 m (6600 ft) with 1 % derating per each additional 100 m. Table 8-5: UPS environmental specifications *Maximum recommended operating and storage temperature with VRLA batteries is +25 °C.
9 Warranty The product is warranted against defects in materials and workmanship for a period of twelve (12) months from its original date of purchase. The local office or distributor may grant a warranty period different to the above. Please refer to local terms of liability as defined in the supply contract.
10 Installation checklist All packing materials and restraints have been removed from each cabinet. Each cabinet in the UPS system is placed in its installed location. A cabinet grounding/mounting kit is installed between any cabinets that are bolted together. All conduits and cables are properly routed to the UPS and any ancillary cabinets. All power cables are properly sized and terminated. Neutral conductors are installed or bonded to ground as per requirements. A ground conductor is properly installed.
Jumper is installed on EPO between pins 1 and 2 if EPO is used in the NC configuration. Alarm relays and signal inputs are wired appropriately. (OPTIONAL) A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet. (OPTIONAL) Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.
11 APPENDIX A: User settings The UPS has the following settings that are user modifiable. In the Home screen, select Settings. User settings: Setting Description Info Information on the UPS model, including part number and serial number. About Version information. GSM GSM Modem. Call Service Send automatic e-mail to service center in case of a failure. Table 11-1: User settings To modify the Config settings, you need to sign in. Setting Description Language Change the user interface language.
Setting Description Config P/W level 2 Change the level 2 password. The default value is 101.