Installation guide
26 30-200 kW P-164000249
User's and Installation Guide Revision 2
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-2:
UPS cabinet weights on page 26, and the size requirements shown in Table 3-1: Dimensions on
page 26, Figure 3-2: 93PM 30-150 kW UPS dimensions on page 28, Figure 3-3: 93PM 160-200
kW UPS dimensions on page 29, Figure 3-4: Eaton 93PM 80-150 kW UPS Top air exhaust kit
dimensions on page 29, and Figure 3-5: Eaton 93PM 200 kW UPS Top air exhaust kit dimensions
on page 30.
30-150 kW 160-200 kW
Shipping dimensions (WxDxH) 760 x 1100 x 2060 mm 900 x 1135 x 2035 mm
Cabinet dimensions (WxDxH) 560 x 914x 1876 mm 760 x 914 x 1876 mm
Table 3-1: Dimensions
30-50 kW 80-100 kW 120-150 kW 160-200 kW
Shipping weight 895 kg 360 kg 440 kg 635 kg
Installed weight 825 kg 290 kg 370 kg 555 kg
Floor loading 1600 kg/m² 570 kg/m² 720 kg/m² 800 kg/m²
Table 3-2: UPS cabinet weights
The UPS cabinets use forced air cooling to regulate internal component temperature. By standard, air
inlets are in the front of the cabinet and outlets are in the back. You must allow clearance in front of
and behind each cabinet for proper air circulation.
With the optional top air exhaust kit, it is possible to configure the air outlets in the top rear of the
cabinet. With this option, the UPS can be installed against a wall or back-to-back.
The clearances required around the UPS cabinet in both of these situations are shown in Table 3-3:
UPS cabinet minimum clearances on page 26 and Table 3-4: UPS cabinet minimum clearances
with top air exhaust kit on page 27. In addition, a minimum of 20 mm clearance is recommended
on the right and left side of the cabinet.
30-50 kW 80-100 kW 120-150 kW 160-200 kW
From top of cabinet 500 mm 800 mm 800 mm 800 mm
From front of cabinet 900 mm 900 mm 900 mm 900 mm
From back of cabinet 200 mm* 400 mm* 500 mm* 500 mm*
Table 3-3: UPS cabinet minimum clearances
*Cabling may require more space.