Installation guide

32 30-200 kW P-164000249
User's and Installation Guide Revision 2
Rated
power
Rated
voltage
Rectifier
input
Rated
current
Rectifier
input
Max.
current
UPS
Output/
Bypass
Rated
current
UPS
Output/
Bypass
Max.
current
Battery
Rated
current
Battery
Max.
current
400 V 76 90 74 87 121 158
415 V 73 86 71 83 121 158
380 V 127 164 122 145 193 231
400 V 121 156 116 138 193 231
80 kW
415 V 116 150 112 133 193 231
380 V 159 196 152 181 241 289
400 V 151 186 145 172 241 289
100 kW
415 V 145 179 140 166 241 289
380 V 190 235 182 218 290 346
400 V 181 223 174 206 290 346
120 kW
415 V 174 214 168 199 290 346
380 V 238 294 228 272 362 433
400 V 226 279 218 258 362 433
150 kW
415 V 217 268 210 249 362 433
380 V 254 328 244 289 386 463
400 V 241 311 231 275 386 463
160 kW
415 V 232 300 223 265 386 463
380 V 317 391 304 362 483 578
400 V 301 371 289 344 483 578
200 kW
415 V 290 358 279 331 483 578
Table 3-7: Rated and maximum currents for rated power and voltage
See the following table for power cable terminations.