Battery quantity 30-50 kW units: 36 blocks, 216 cells per battery string
80-200 kW units: 36 blocks, 216 cells per battery string, or 40
blocks, 240 cells per battery string
Note! Battery strings with different battery quantity and voltage may not
be connected in parallel!
Battery voltage 432 V (36 blocks) or 480 V (40 blocks)
Recharge profile ABM or float charge
End of discharge voltage 1.67 VPC to 1.75 VPC, configurable or automatic (load adaptive)
Charge current
30-50 kW units
80-100 kW units
120-150 kW units
160-200 kW units
Configurable:
Default 12 A, max 22 A (common for internal and external batteries
Default 24 A, max 44 A
Default 36 A, max 66 A
Default 48 A, max 88 A
Battery start option Yes
Table 8-4: Battery specification
Note! For external battery connection, 24 VDC Shunt Trip signal wiring from the UPS must be
connected to the auxiliary signal connection of the battery breaker.
8.5 UPS environmental specifications
Acoustic noise at 1 m 30-50 kW: <60 dBA
80-200 kW: <65 dBA
ESS operation: <45 dBA
Ambient UPS storage temperature range From -25 °C to +55 °C in the protective
package*