Specification

CORE Lighting Controls
2. ASPIRE Receptacle Components
a. All receptacles shall be UL Listed, CSA and NOM approved.
b. Receptacles shall be two-pole, three wire ground and rated for 15A or 20A at 125VAC. All
receptacles shall be NEMA configuration type 5-15R or 5-20R.
c. Receptacles shall be available in single (9507TR, 9508TR) and duplex (9505TR, 9510TR) models.
d. Ground-fault interrupter receptacles (GFCI) shall be two-pole, three-wire ground and rated 15A
(9566TR) or 20A (9569TR) at 125VAC Configuration shall be of the duplex type with rectangular
NEMA WD-6 design. Receptacles shall have a 5 milliampere ground-fault trip level and a 0.025 sec.
response time with "test" and "reset" buttons.
e. All receptacles shall provide compliance with the 2008 NEC® section 406.11 specification that
states all receptacles installed in dwelling units must be tamper resistant.
3. ASPIRE Telephone Jack and Cable TV Jack Components
a. Contractor shall provide an appropriate barrier (partition) to isolate jack from high-voltage wiring
when ganged with a dimmer, fan-speed control, switch, or receptacle. This complies with NEC Articles
800-3 and 820-13.
b. Data jack (9557) shall be designed to mate with standard 8-conductor modular jacks and be
compatible with 2, 4, 6, 8 conductor lines.
c. Telephone jack (9556) shall be designed to mate with standard 4- or 6-conductor modular jacks,
and be compatible with 2, 4, or 6 conductor lines. Telephone jacks shall meet FCC Part 68, paragraph
F standards to ensure compatibility with U.S. telephone systems.
d. Cable TV jacks (9555) shall be the coaxial type, designed for use with standard 75-Ohm cables.
C. ASPIRE Screwless Wallplates
1. Wallplates shall be manufactured from durable polycarbonate plastic with gloss finish, and shall attach to
the basic components without using exposed hardware or screws.
2. Multigang wallplates shall provide a continuous, seamless cover for up to six-ganged (9521, 9522, 9523,
9524, 9525, 9526, 9527) decorator-style control and accessory combinations with no exposed hardware or
screws.
3. Modular communication mid-size wallplates shall provide a seamless cover for up to six ports (9550, 9551,
9552, 9553, 9554) for use with jacks and adapters with no exposed hardware or screws.
4. Multigang wallplates shall include an adapter plate for proper device alignment and wallplate attachment.
5. Control, accessory and wallplate profiles shall not exceed 0.30 inches from wall surface to faceplate front
surface.
6. To ensure a precise color match between all plastic parts, color variation of any gloss finish control or
wallplate shall not exceed a delta E of 1, CIE L*a*b* color units, as defined in ASTM E 308-99.
7. Visible parts of dimmers, switches, standard receptacles, cable jacks or any wallplate shall exhibit ultraviolet
stability when tested with multiple actinic light sources as defined in ASTM D4674-89.
2.03 SOURCE QUALITY CONTROL
A. All controls shall be 100% functionally tested at the time of manufacture. Statistical sampling plan shall not be
acceptable.
PART 3 — EXECUTION
3.01 INSTALLATION
A. Contractor shall furnish all devices, labor and other services necessary for the proper installation of the devices as
indicated on the drawings and specified herein.
B. Contractor shall be responsible for de-rating lighting controls capacity in multi-gang installations.