Eaton 9E UPS (40–60 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000302—Rev 1 www.eaton.com/powerquality 9-3
9.2.5 UPS Internal Battery Plus External Battery Cabinet Runtimes (in Minutes) at Full load
UPS Model UPS Rating
Number of UPS
Battery Strings
EBC Model Number of EBCs
Number of EBC
Battery Strings
Runtime
9E–60/40 40 kVA 8 9E 60EBC 1 4 46.0
9E–60/40 40 kVA 8 9E 60EBC 1 6 65.0
9E–60/40 40 kVA 8 9E 60EBC 2 8 85.2
9E–60/40 40 kVA 8 9E 60EBC 2 12 128.0
9E–60/60 60 kVA 8 9E 60EBC 1 4 27.8
9E–60/60 60 kVA 8 9E 60EBC 1 6 39.3
9E–60/60 60 kVA 8 9E 60EBC 2 8 51.5
9E–60/60 60 kVA 8 9E 60EBC 2 12 77.6
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.