Operating instructions

UPS Installation Plan and Unpacking
Eaton 9E UPS (40–60 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000302—Rev 1 www.eaton.com/powerquality 3-3
The UPS equipment operating environment must meet the weight requirements shown in Table 3-3 and the
size requirements shown in Figure 3-1 through Figure 3-4. Dimensions are in millimeters (inches).
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-4.
Table 3-3. UPS Cabinet Weights
Model
Weight
kg (lb)
Shipping Installed Point Loading
Eaton 9E-40 with internal batteries 675 (1488) 590 (1301) 8 at 74 (163)
Eaton 9E–60/40 with internal batteries
765 (1686) 680 (1499) 8 at 85 (187)
Eaton 9E–60/60 with internal batteries
Eaton 9E-40 without batteries
405 (892) Not Applicable Not ApplicableEaton 9E–60/40 without batteries
Eaton 9E–60/60 without batteries
Table 3-4. UPS Cabinet Clearances
From Top of Cabinet 304.8 mm (12") working space
From Front of Cabinet 914.4 mm (36") working space
From Front of Cabinet Minimum 650 mm (25.6") for cooling air intake and door swing
Recommended 914.4 mm (36") working space
From Back of Cabinet Minimum of 203.2 mm (8”) for operation
Recommended 914.4 mm (36") for service
Clearances must comply with all applicable national and local codes. Flexible
conduit may be used to adjust between required operation and service clearances.
From Right Side of Cabinet None Required
From Left Side of Cabinet None Required