Operating instructions
UPS Installation Plan and Unpacking
3-12 Eaton 9E UPS (40–60 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000302—Rev 1 www.eaton.com/powerquality
l
The REPO feature opens all switchgear in the UPS cabinet and isolates power from your critical load. Local
electrical codes may also require tripping upstream protective devices to the UPS.
l
The REPO switch must be a latching-type switch not tied to any other circuits.
l
A jumper wire must be connected between pins 3 and 4 on the REPO terminal block if using a
normally-closed REPO switch.
l
REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG.
l
The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
l
The maximum distance between the REPO and the UPS cannot exceed 150 meters (500 feet).
3.3 Battery Type
The battery types listed in Figure 3-10 are supplied in the UPS Cabinet and external Battery Cabinet. When
purchasing UPS Cabinet or external Battery Cabinet without batteries, only the following types are
recommended. Use of any other battery type inside Eaton cabinets will void the product warranty. When
replacing batteries use the same manufacturer and part number originally supplied with the unit to ensure
correct harness fit and terminal landing.
3.4 Inspecting and Unpacking the UPS Cabinets
The cabinet is shipped bolted to a wooden pallet and protected with an outer wood container (see Figure 3-5).
WARNING
The UPS cabinet is heavy (see Table 3-3). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION
Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service
representative immediately.
Table 3-10. Battery Type
Battery Manufacturer CSB Battery Technologies Inc. G.S. Yuasa
Battery Model HRL1234WF2FR REW45-12FR
Battery Quantity 9E-40 108 108
Battery Quantity 9E–60/40 144 144
Battery Quantity 9E–60/60 144 144
NOTE For the following step, verify that the forklift or pallet jack is rated to handle the
weight of the cabinet (see Table 3-3 for cabinet weight).










