User manual

3
.
Installation
3.8
Installation requirements
Recommended protective devices and cable cross-sections
1.
Recommended upstream protection
UPS power rating Upstream circuit breaker
5000VA D curve – 32A
6000VA D curve – 32A
2 poles circuit breaker
L1
to UPS Normal AC source
Recommended cable cross-sections
Terminal wire
Minimum input
Tightening
size rating wire size torque
4-16 mm
2
(12-6 AWG) 6 mm
2
(10 AWG) 105°C
10 lb in
10 mm
2
(8 AWG) 75°C
Copper wire, solid or stranded.
Page 21
N(L2)
G N(L2) L1
2.
5-6kVA EU_EN
Terminal Wire
position
function
L1
Phase
N(L2)
Neutral
(Phase)
Ground