11. Specifications
Agency markings CE / cULus / NOM
Operating temperature 32 to 104°F (0 to 40°C) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 32 to 104°F (0 to 40°C) with batteries
5 to 140°F (-15 to 60°C) without batteries
Transit temperature -4 to 122°F (-20 to 50°C)
Relative humidity 0 to 95% no condensing
Operating altitude Up to 2,000 meters (6,562 ft) above sea level with 10% derating per 1000m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 55 dBA at 1 meter typical
Table 9. Battery
Internal batteries EBM
Rack / Tower
configuration
9PX6KSP: 240Vdc (±120Vdc) 9PXEBM240SP: 240Vdc (±120Vdc)
Type
CSB/HR1227WF2FR
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 77°F (25°C).
Lifetime is reduced above 86°F (30°C).
Monitoring Advanced monitoring for earlier failure detection and warning
Battery port External three-pole SBS75G Blue + SBS75G Black connectors on UPS for
connection to EBM
EBM battery cable
length
40cm (15.7in)
Table 10. Communication options
Communication bay (1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Relay output contacts (4) relay outputs (normally open or normally closed)
Remote On/Off 2 pins jumper (normally closed)
Remote Power Off 3 pins jumper (pin 1 & 3 normally closed)